Utica Boilers UB95M-200 Installationsanweisungen

Seite von 52
Refer to Repair Parts Manual for illustrations, and Control 
Manual and Troubleshooting Guide for detailed sequence of 
operation and troubleshooting guide.
11.1 Aluminum Heat Exchanger
• Monoblock design cast aluminum heat exchanger 
eliminates need for mating sections eliminates leaks 
between sections. 
• Cast aluminum has better heat transfer properties 
which leads to higher efficiency and cooler exhaust 
temperatures. 
• Cooler exhaust temperatures create condensation of 
flue gas, which would cause corrosion in traditional cast 
iron heat exchangers.
11.2 Main Power Switch
Main power switch is located on the display panel. Main power 
switch is illuminated when receiving power and in ON position.
11.3 Modulating Boiler Control
Integrated modulating control senses load necessary 
to heat structure and therefore uses less fuel than 
conventional fixed firing rate boiler when there is lower 
than peak demand for heat.
Control senses supply water, return water, and outside 
air temperatures. If outside air sensor is connected and 
calculates load on system it adjusts firing rate to deliver 
amount of heat needed at that particular time.
11.4 NTC Sensors
NTC sensors measure supply water, return water, and 
outside air temperature. Configured to operate with 
modulating boiler control.
11.5 Modulating Blower
• Modulating blower provides introduction of gas/air 
mixture through burner and into combustion chamber 
then out  exhaust vent where combustion products are 
discharged to outdoors. 
• Blower is designed to communicate with modulating 
control to run at variable speeds dependent on heating 
system heat load. 
• Variable speeds create pressures felt by gas valve and 
gas/air mixer that dictate how much fuel is introduced 
to combustion process.
11.6 Gas Control Valve
• Boiler gas controls have been developed for domestic 
heating appliances with premix burners and automatic 
direct burner ignition and are suitable for natural and 
LP gas. 
• Gas controls perform all functions required to safely 
regulate gas flow to main burner of boiler. 
• Gas valve is directly connected to gas/air mixer.
11.7 Gas/Air Mixer
Venturi design of gas/air ensures correct mixture of air and 
gas.
11.8 Modulating Burner
Burner is designed to operate over full range of input. 
Burner can operate under normal (blue flame) and infrared 
conditions.
11.9 Direct Spark Igniter (DSI)
Boiler uses DSI to ignite fuel/air mixture in combustion 
chamber and sense flame during operation. DSI is durable, 
reliable, and resists breakage.
11.10 Manual Reset Low Water Cut Off
• Installed integral low water cut off (LWCO) must be 
manually reset if there is a low water condition. 
• LWCO senses water through probe at boiler top that 
sends signal through water to ground. If the signal is 
not sensed LWCO enters lockout mode that disables 
boiler. 
• LWCO in normal mode illuminates red indicator light on 
LWCO panel in boiler. 
• During low water condition, red light goes out and 
LWCO and control reset buttons on display panel must 
be pressed to reset LWCO.
11.11 Normally Closed LWCO Switch
• Round button switch located next to digital display is 
normally closed and spring loaded, when depressed will 
open, when pressure is removed closes. 
• Switch is used as manual reset for LWCO. LWCO will 
remain in lockout when tripped until water level reaches 
probe and switch is pressed to open state and then 
released to closed state, which sends signal to LWCO to 
resume normal operation. 
• Boiler control reset button must then be pressed to 
reset from low water condition. LWCO switch and 
control reset button are located on boiler panel display.
11.12 High Limit Control
• High limit control is safety limit control provides 
protection for boiler and heating system from unsafe 
operating conditions which could damage the boiler. 
11 - CONTROLS AND ACCESSORIES
21