Utica Boilers UB95M-200 Installationsanweisungen

Seite von 52
Water Treatment And Freeze Protection - See 
Appendix B
12.1 Filling Boiler With Water And Purging Air
1. 
Systems With Diaphragm Type Expansion Tanks
A.  Close all zone service valves on supply and return 
piping. Open feed valve and fill boiler with water. 
Verify air vent is open. Hold relief valve open until 
water runs air free for five seconds to rapidly bleed 
air from boiler, then let relief valve snap shut.
B.  Open zone service valve on supply pipe for first 
zone. Open purge valve on first zone. Feed water 
will fill zone, pushing air out purge valve. Close 
purge valve when water runs air free. Close zone 
service valve.
C.  Repeat step 2 for all remaining zones.
D.  Open all service valves. Any air remaining trapped 
in return lines between service valves and boiler 
will be pushed towards air vent when boiler is 
placed in operation.
E.  Inspect piping system and repair any leaks 
immediately.
12 - BOILER STARTUP
2. 
Systems With Conventional Closed Type Expansion 
Tanks
A.  Close all zone service valves on supply and return 
piping and close expansion tank service valve. 
Drain expansion tank. Open feed valve and fill 
boiler with water. Hold relief valve open until water 
runs air free for five seconds to rapidly bleed air 
from boiler, then let relief valve snap shut.
B.  Open zone service valve on supply pipe for first 
zone. Open purge valve on first zone. Feed water 
will fill zone, pushing air out purge valve. Close 
purge valve when water runs air free. Close zone 
service valve.
C.  Repeat step 2 for all remaining zones.
D.  Open expansion tank service valve and tank 
vent. Fill tank to proper level and close tank vent. 
Remove handle from expansion tank service valve 
so it is not accidentally closed.
E.  Open all service valves. Any air remaining trapped 
in return lines between service valves and boiler 
will be pushed towards expansion tank when boiler 
is placed in operation.
F.  Inspect piping system. Repair any leaks immediately.
NOTICE
Do not use stop leak compounds. Repair leaks in 
threaded connections of aluminum boiler sections. 
Aluminum threads do not seal themselves.