Utica Boilers UB95M-200 Installationsanweisungen

Seite von 4
!
  
WARNING
Install boiler so gas ignition system components 
are protected from water (dripping, spraying, 
rain, etc) during appliance operation and service 
(circulator replacement, etc).
This addendum applies to series:
UB90, UB95, Q90, Q95M, K90, K95M, BW9 & GWB9, FW95M & OL95M
!
  
WARNING
You MUST follow these instructions to prevent 
damage to boiler’s heat exchanger caused by 
inadequate dielectric isolation, incorrect water 
treatment or antifreeze application. Failure to 
comply could result in possible severe personal 
injury, death or substantial property damage. 
Instructions in this addendum replace all related 
information in Boiler Installation Manual, User’s 
Manual, or any other supplemental instruction or 
addendum.
Apply this information in place of any related 
information in Installation, Operation & 
Maintenance Manual Accompanying this boiler.
• DIELECTRIC ISOLATION
Two (2) 1-1/4” X 1-1/4” Female to female 
dielectric isolation unions are shipped loose 
in boiler parts bag. Install Dielectric Isolation 
unions at boiler supply line and return line. Install 
isolation fi ttings nearest boiler prior to system 
piping connections.
• WATER TREATMENT and ANTIFREEZE 
PROTECTION
MUST be applied for ALL aluminum series 
high effi ciency gas-fi red boilers using antifreeze 
protection.
 
P/N# 240006888, Rev. E [06/2011]
Aluminum Series
High Effi ciency Gas-Fired Boiler
DIELECTRIC ISOLATION & 
ANTIFREEZE PROTECTION 
ADDENDUM