System and Operating Precautions
Applies to ALL Aluminum High Effi ciency Gas-Fired Water Boilers
!
  
WARNING
Eliminate System Leaks
Continuous addition of make-up water will 
constantly add oxygen to system. Eliminate 
all system leaks. All system leaks must be 
repaired immediately. 
Verify expansion tank is operational and 
properly sized. Undersized expansion tanks 
cause relief valve weeping and substantial 
make-up water addition.
Operation of this boiler in system containing 
signifi cant amounts of dissolved oxygen 
can cause severe heat exchanger corrosion 
damage.
This boiler is not designed for use in systems 
containing regular additions of make-up 
water. Regular additions of make-up water 
may cause severe heat exchanger damage.  
System leaks may not always be visible. An 
unseen system leak will become obvious if 
boiler pressure decreases when make-up 
valve is closed. 
This boiler is designed for closed loop hydronic 
heat system ONLY! This boiler is not suitable 
for natural gravity type installations, or any 
other open type system.
!
  
WARNING
Clean the System First
BEFORE
 connecting boiler to heating system, 
clean and fl ush system thoroughly. Verify 
system is free of sediment, fl ux and any 
residual boiler water additives.
Systems having antifreeze not recommended 
must be completely fl ushed to ensure no 
old antifreeze remains. In older systems 
obviously discolored, murky or dirty water; or 
pH reading outside acceptable range (between 
7.0 and 8.0) are indications the system 
should be cleaned or treated. Thoroughly 
fl ush system with clean water to remove any 
sediment or contaminants. Sludge and iron 
oxide deposits can cause rapid breakdown of 
inhibitors.
Flushing with clean water. If chemical cleaners 
are used, use only those recommended 
for use with aluminum boilers. Follow 
chemical cleaner manufacturer’s instructions 
completely.
DO NOT mix different manufacturer’s 
products.
!
  
WARNING
Fill Water and Chemistry
Verify water used to fi ll system meets these 
requirements:
System fl uid pH maintained between 7.0 
and 8.0. 
Maintain water hardness below 7 grains 
hardness. 
Filling with chlorinated potable water is 
acceptable. DO NOT fi ll boiler with water 
containing chlorine in excess of 100 ppm.
DO NOT use inhibitors or other additives that 
are not listed at the end in this addendum.
Consult local water treatment specialist 
for recommendations if any of above 
requirements is outside stated ranges.