Siemens SIMATIC NET CP 343-1 Benutzerhandbuch

Seite von 22
english
11
Product information CP 343–1 
C79000–Z8964–C038–05
Status on the  FC call interface; special situation with FC versions
With the FCs AG_SEND (FC 5) and AG_RECV (FC 6), you receive the follo-
wing return values after a connection is aborted:
S
AG_SEND: DONE=1; ERROR=0; Status=0000
H
S
AG_RECV: DONE=0; ERROR=1; Status=8183
H
The new FCs for longer data fields (FC AG_LSEND and AG_LRECV) react in
exactly the same way to a connection abort, in other words with the return
values
S
DONE=0; ERROR=1; Status=8183
Influence of MPI Connections on Connections via Industrial Ethernet
If a station on MPI is added or removed, for example because a service PG
has been connected or disconnected, it is possible that all the connections on
the communications bus are aborted. This has the following effects on the
communication connections on Industrial Ethernet:
S
All S7 connections are temporarily aborted.
S
The ISO Transport connections on which a job with a data length > 240
bytes is being processed are aborted.
The return values must be handled accordingly on the FC interface in the
user program.
2
Installation
2.1
Module Accessories
The accessories required to attach the CP 343-1 to an Industrial Ethernet
LAN must be ordered separately. For more detailed information, see /9/, /10/,
/12/.