Trane Modular 20 to 35 Tons Entwickleranleitung

Seite von 52
Programming SETUP
24
 PKG-SVP01D-EN
Supply Air Temp Reset Type:
Used With: Units without heat
Factory Presets: None
Possible Values: Cooling = None, Zone, OA
Cooling: ZONE
1.
Press the NEXT key until the following screen is displayed.
Supply Air Temp Reset Type:
Heating: ZONE
Used With: Units with hydronic heat
Factory Presets : None
Possible Values: Cool/Heat = None, Zone, OA
Cooling: ZONE
 
1.
Press the NEXT key until the following screen is displayed.
Supply Air Temp Zone               Reset For Cooling:
Used With: Units when Zone Cooling Reset is 
selected.
Possible Values: Cooling/Heating = Zone, OA; 
Start Temp Zone = 209 OS = 70; End Temp Zone 
= 210 OA = 71
Start Temp: 72 F
                 End Temp:      69 F
1.
Press the NEXT key until the following screen is displayed.
Supply Air Temp Outside Air     Reset For Cooling:
Possible Values: Cooling/Heating = Zone, OA; 
Start Temp Zone = 209 OS = 70; End Temp Zone 
= 210 OA = 71
Start Temp: 90 F
                 End Temp:      70 F
1.
Press the NEXT key until the following screen is displayed.
Supply Air Temp Zone               Reset For Cooling:
Used With: All Units when Outside Air cooling 
reset is selected.
Possible Values: SAT = Zone, OA; Reset 
(Zone) = 72; Reset (OA) = 72
Maximum Amount of Reset Applied:
                    5 F
1.
Press the NEXT key until the following screen is displayed.
 
Supply Air Temp Outside Air     Reset For Cooling:
Used With: All Units when Outside Air cooling 
reset is selected.
Possible Values: SAT = Zone, OA; Reset 
(Zone) = 72; Reset (OA) = 72
Maximum Amount of Reset Applied:
                    5 F
1.
Press the NEXT key until the following screen is displayed.
 
Supply Air Temp Outside Air               Reset For Heating:
Used With: All Units when Outside Air heating 
reset is selected.
Factory Presets: Start = 10 F; End = 60 F
Possible Values: Start OA Temp = 73 F; End 
OA Temp = 74 F
Start Temp:    10 F                    End Temp:      60 F
1.
Press the NEXT key until the following screen is displayed. 
Supply Air Temp Zone             Reset For Heating:
Used With: Units when Zone Air heating reset 
is selected.
Factory Presets: Start = 65 F, End = 68 F
Possible Values: Start OA Temp = 211; End 
OA Temp = 212
Start Temp:    65 F                    End Temp:      68 F
1.
Press the NEXT key until the following screen is displayed. 
Supply Air Temp OA               Reset For Heating:
Used With: All Units when Zone Heating is 
selected.
Possible Values: SAT temp = Zone, OA; Zone 
Reset = 75; OA Reset = 75
Maximum Amount of Reset Applied:                   10 F
1.
Press the NEXT key until the following screen is displayed. 
Supply Air Temp Zone               Reset For Heating:
Used With: All Units when outside heating is 
selected.
Possible Values: SAT temp = Zone, OA; Zone 
Reset = 75; OA Reset = 75
Maximum Amount of Reset Applied:                   10 F
1.
Press the NEXT key until the following screen is displayed. 
VAV Box Max Stroke Time:                                   0 Min
Factory Presets: 6 Min
Possible Values: 0 to 10
1.
Press the NEXT key until the following screen is displayed.
Max Occupied IGV/VFD Command:                      100%
Used With: Units with IGV/VFD installed
Factory Presets: 100%
Possible Values: 0 to 100%
1.
Press the NEXT key until the following screen is displayed.