Trane Modular 20 to 35 Tons Entwickleranleitung

Seite von 52
22
 PKG-SVP01D-EN
Programming SETUP
After the unit is installed, the control module must be 
programmed with certain SETUP information in order to 
operate and function properly. The data necessary for unit 
operation will vary depending on certain factors such as 
unit size, type, and installed options.
This section of the manual provides step by step 
instructions for programming this information. Also 
provided are instructions for checking unit operating 
status, accessing and clearing diagnostics, and 
performing service tests.
Some of the displays shown in this manual may not 
appear on the Human Interface (HI) LCD screen during 
programming. Only the applicable screens for the specific 
unit options and operating parameters will be displayed.
Ignore the steps that do not apply to your unit and 
application, and move on to the next applicable set of 
instructions in the manual. Continue this process until all 
applicable screens are programmed with the required 
information. 
SETUP Menu
The SETUP menu is used to input initial operating 
information such as control parameters, SETPOINT source 
selection, sensor source selections, ventilation override 
definitions, functions enable/disable, status, text display 
(language), temperature display (C or F), and system 
tuning parameters. When a SETUP screen is displayed for 
30 minutes without a key being pressed, the LCD screen 
will revert to the appropriate power-up display. If this 
happens, press the SETUP key again to return to the 
SETUP menu.
Note: Many of the screens displayed in this section are 
applicable only for the options that are installed in 
the unit and may not be visible on your unit. 
Press the SETUP key to begin viewing or modifying the 
SETUP screens.
If a screen is not visible on the Unit Human Interface 
Module, refer to the “Used With” information listed to the 
right of each screen in this book.
Follow this procedure when viewing a screen that requires 
modification:
1.
Press the + or - key until the proper value displays.
2. Press the ENTER key to confirm your choice.
3. Press the NEXT key to advance the cursor.
4. Repeat steps 1 and 2 if there are addtional values on the 
same screen that require changing.
SETUP Menu Screens
Press the SETUP key to display the following screens.
Display Text in: 
 ENGLISH LANGUAGE
Display Units Using:
ENGLISH NOTATION
Used With: All Units
Factory Presets: Text and Units: ENGLISH 
Language, ENGLISH Notation
Possible Values: Text: ENGLISH, FRENCH, 
SPANISH; Units: ENGLISH NOTATION, SI 
NOTATION
1.
Press the NEXT key until the following screen is displayed.
Unit Control:
Unit Address:
LOCAL
31
Used With: Units with TCI, LCI or BCI module
Factory Presets: Control = Local, Address = 1 
(only shown if TCI installed) 
Possible Values: Unit Control = Local, BAS/
NETWORK, Unit address= 0-31 (only shown if 
TCI installed)
1.
Pressing the NEXT key will bypass this section.
General Unit Functions Setup Submenu
Press ENTER to Review or Adjust
1.
Pressing the NEXT key will bypass this section.
Supply Fan VFD Mode:
BYPASS
Used With: Units with VFD and bypass
Factory Presets: Mode = Normal, Address = 1
Possible Values: Mode = Normal, Bypass
1.
Pressing the NEXT key will bypass this section.
If Remote Panel Mode Input Not Present:
System Mode:   AUTO
Possible Values: System Mode = OFF/AUTO
1.
Press the NEXT key until the following screen is displayed (if applicable).
Daytime Warmup Function:               DISABLED
Factory Preset: Disabled
Possible Values: Daytime Warm up Function: 
ENABLED, DISABLED
1.
Press the NEXT key until the following screen is displayed.