PRE-ENERGIZATION CHECK 
Page 21 
 
 
 
 
MANUAL OPERATION 
 
Powerful springs.  Do not 
place your hands or any 
part of your body inside 
the circuit breaker while 
the indicators show 
CHARGED (yellow) or ON 
(red). 
 
To avoid damaging the 
mechanism, do not close 
the circuit breaker when 
the On-Off Indicator shows 
ON (red). 
 
MANUAL CLOSING: 
 
1. Check to make sure that the On-Off 
indicator shows OFF (green). 
  
2.  Attach the charging handle to the breaker if it 
is not already attached. 
 
3.  If the closing spring status indicator shows 
DISCHARGED (white): 
 
Turn the closing handle clockwise 3 to 5 
times to charge the closing spring (Fig. 25).  
(Closing Spring Status Indicator changes to 
CHARGED, Yellow)  When the handle is 
released, it returns to its normal position, and 
do not attempt to turn again. (Fig. 26) 
 
If the closing spring status indicator shows 
CHARGED (yellow): 
 
Do not attempt to turn handle. 
 
Pushing the Green lever in the direction of 
the arrow closes the circuit breaker (On-Off 
indicator changes to ON) 
 
 
 
 
 
 
 
 
 
 
 
 
Fig. 25  Preparing to Manually Close Breaker  
 
 
 
 
 
 
 
 
 
Fig. 26  Manually Charging Breaker 
 
 
    WARNING 
    CAUTION 