OPERATION Page 
19 
 
 
 
 
 
MOVING THE CIRCUIT BREAKER FROM 
THE DISCONNECTED TO THE CONNECTED 
POSITION 
 
Hazard of fire, explosion, 
severe injury, death and 
property damage.  Circuit 
breaker must be OFF before 
moving to or from the 
CONNECTED position. 
 
Do not move the circuit 
breaker to the CONNECTED 
position without first 
connecting the secondary 
control circuit plug.  Do not 
disconnect the plug while 
the breaker is in the 
CONNECTED position. 
 
Any time the circuit breaker is connected to main 
power, it is necessary that the control circuit plug 
be connected to ensure that the tripping circuit is 
completed. 
 
TO MOVE THE CIRCUIT BREAKER TO THE 
CONNECTED POSITION: 
 
1. Connect the control circuit plug to the 
breaker (Fig. 21). 
  
2.  Check to be sure that the On-Off Indicator 
reads OFF (Green).  Push the manual trip 
lever in the direction of the arrow if 
necessary to open the circuit breaker.  The 
interlock release lever cannot be raised 
unless the circuit breaker is OFF. 
 
3.  Grasp the handles on the breaker with both 
hands and, while lifting the interlock 
release lever with the left hand, push the 
breaker into the cell until the arrow on the 
front cover indicates the CONNECTED 
position has been reached (Fig. 22), then 
release the lever.  Check to make sure the 
interlock release lever has returned to its 
original lowered position. 
 
 
 
 
 
Fig. 21  Control Circuit Plug Connected to 
Breaker 
 
 
 
 
 
 
Fig. 22  Breaker at CONNECTED Position 
    
DANGER
 
    WARNING 