1.1.3 Design 
Specifications 
 
Type of Load: 
Three phase AC induction motors 
AC Supply Voltage: 
Universal, 208 - 600VAC ±10%, 50/60 Hz 
Power Ratings: 
18 - 1250 Amps, 7.5 - 1000 HP @ 460V 
Unit Capacity - Continuous 
Max. Amp rating is UL Listed continuous rating 
Unit Capacity - Overload Rating 
(Percent of motor FLA) 
350% - 30 seconds 
600% - 10 seconds 
Power Circuit 
6 SCRs, full phase angle firing using a hard fire picket firing circuit and “Back 
Porch” DC carryover to avoid motor transient problems 
SCR Firing Angle Detection 
6 pulse Independent Locked Phase Tracking with Auto-synchronization, 
prevents misfiring on unstable source frequency 
SCR PIV Ratings  
(Peak Inverse Voltage) 
1600V 
Phase Rotation 
Operates with any phase sequence, or  
programmable rotation trip ABC / ACB / Off 
Transient Protection  
RC snubber dv/dt networks on each phase 
Cooling 
Fan assisted convection 
Bypass Contactor 
Standard on all NEMA 12 enclosed units 
Units 160A and less:  Standard on all open panel units (-BP versions) 
Units 210A and over:
Optional on open panel units (-BP versions) 
Bypass Contactor Rating
Shunt rated or can be sized for Line start rated contactor (see charts) 
Bypass Contactor Control
Integral control is included, but contactor can be externally controlled as well. 
Ambient Condition Design 
Open panel mount units: 0° to 50 °C (32° to 122°F) 
Factory enclosed units: 0° to 40°C (32° to 104°F) 
5 - 95% relative humidity 
0 - 3300 ft. (1000m) above sea level without derating 
Control Power  
120VAC (customer supplied), 240VAC optional 
Inputs 
6 Dry (voltage free) contact inputs using 24VDC from an internal power supply 
Programmable Outputs 
3 relays, 2 each Form C (SPDT), 1 each Form A (SPST). 
Can be programmed for 26 functions, with delays or flashing. 
Output Relay Contact Rating  5 Amps, 240VAC max. (1200VA) 
Dedicated Fault Output 
AC Triac solid state switch 
240VAC/DC, 50mA max. 
Approvals  
UL Listed, Canadian UL (cUL) Listed, CE Approved