Toshiba 18 - 1250 A Benutzerhandbuch

Seite von 99
TE Series        
          Digital Solid State Soft Starters   18 – 1250A 
1.2  
Sizes and Ratings 
The Toshiba TE Series starters are current rated controllers. Max. Amp 
ratings are for continuous duty and must not be exceeded. Always 
check the motor nameplate FLA and Service Factor to ensure proper 
sizing. 
  
Each size has an adjustable range of current from 50% to 100% of the 
Max Amp rating. Table 1.2 below shows the Current Ratings available. 
 
1.2.1      Selecting for Service Factor Utilization 
Many NEMA design motors include a design rating referred to 
as Service Factor (SF) that may allow continuous operation 
above the nameplate current rating. If using this Service 
Factor, the TE Series starter must be sized for the total amps 
used. For proper selection of the TE Series starter when using 
SF continuously, multiply the nameplate FLA by the stated 
Service Factor, or use stated Service Factor Amps (SFA) if 
listed on the nameplate. Following is an excerpt from the 
NEMA MG-1 standards for AC Motors that describes the 
issues concerning the use of Service Factor ratings. 
 
"When an induction motor is operated at any service factor 
greater than 1.0, it may have efficiency, power factor and 
speed different than those at rated load. Locked rotor torque 
and current and breakdown torque will remain the same. A 
motor operating continuously at any service factor greater than 
1.0 will have a reduced life expectancy compared to operating 
at its nameplate horsepower.
 
 When using this feature, simply program the TE Series 
Service Factor (F002) to the nameplate rating see section 
5.6.1. All other adjustments to protection circuits are done 
automatically within the TE Series. 
 
1.2.2       Selecting for Across the Line Bypass 
If you need to be able to start the motor Across-the-Line if the 
TE Series electronics are out of service, the starter can also 
be selected based upon the rating of the Bypass Contactor. 
Some users may also elect to size their Bypass Contactors per 
NEMA guidelines. Please use the Product Price Catalog for 
details and notes on doing this, and see Appendix 5 for special 
considerations regarding Overload Protection. 
 
 
ƒ  NOTE:  
The TE…-BP Series starters include the ability to connect a dry 
contact directly to the Bypass Contactor coil control circuit. These 
terminals shipped are covered and should be used ONLY when 
necessary for Emergency Bypass operation and with an external 
Overload Relay. See Appendix 5 for additional information. 
 
No field wiring is necessary to these terminals if this feature is not 
used. 
 
 
Model  
Number 
Current 
Range 
Min. - Max. 
TE-18-BP 
9 - 18 
TE-28-BP 
14 - 28 
TE-39-BP 
19 - 39 
TE-48-BP 
24 - 48 
TE-62-BP 
36 - 62 
TE-78-BP 
39 - 78 
TE-92-BP 
46 - 92 
TE-112-BP 
56 - 112 
TE-150-BP 
75 - 150 
TE-160-BP 
80 - 160 
TE-210-BP or -P 
105 - 210 
TE-275-BP or -P 
138 - 275 
TE-360-BP or -P 
180 - 360 
TE-450-BP or -P 
225 - 450 
TE-550-BP or -P 
275 - 550 
TE-718-BP or -P 
359 - 718 
TE-900-BP or -P 
450 - 900 
TE-1006-BP or -P 
503 - 1006 
TE-1250-BP or -P 
625 - 1250 
 Table 1.2: TE Series Range