Toshiba 18 - 1250 A Benutzerhandbuch

Seite von 99
TE Series        
          Digital Solid State Soft Starters   18 – 1250A 
    WARNING
 
2.4  
SERVICE WARNING! 
Do not service equipment with voltage applied! The unit can be the 
source of fatal electrical shocks! To avoid shock hazard, 
disconnect main power and control power before working on the 
unit. Warning labels must be attached to terminals, enclosure and 
control panel to meet local codes. Use Lock Out tags such as the 
one shown when servicing equipment. 
 
2.5  
Mounting and Cleaning 
When drilling or punching holes in the enclosure, cover the electrical 
assembly to prevent metal filings from becoming lodged in areas which 
can cause clearance reduction or actually short out electronics. After 
work is complete, thoroughly clean, vacuum the area, and re-inspect the 
unit for foreign material.  
2.5.1 Clearances 
Make sure there is sufficient clearance all around the unit for cooling, 
wiring and maintenance purposes. To conserve panel space, the TE 
Series
 –BP models were designed for close horizontal clearances of 
only 1 inch (25mm) on either side. A minimum vertical clearance of 4” 
(100 mm) on the top and bottom is necessary to maximize effective 
airflow and cooling, and the unit must be installed with its heat sink ribs 
oriented vertically and running parallel to the mounting surface. Keep in 
mind that these are minimums. Wiring may require more clearance, 
particularly on the bottom. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Figure 2.5:  TE minimum mounting clearances 
  TE Series
Starter
1" minimum (25  mm)
1" minimum (25
 
 mm)
4" minimum ( 100 mm )
4" minimum ( 100 mm )