          Digital Solid State Soft Starters   18 – 1250A 
24 
Display
Press
Key...
Shows...
M e ans...
Phase  A
Current
Phase  B
Current
Phase C
Current
Remaining
The rmal Capacity
Ground Fault
Current
Proce ss Timer
Re maining Time
0120.
0121
0120
H083
G002
0060
13.. 30
Time Clock
Time Base
Loop Back to
Phase  A Curre nt
Figure 5.3.1: Reading the Status Display
0120.
5.3  
Display Modes 
There are three modes of display: the Status Display Mode, the 
Program Mode, and the Fault Mode. 
 
5.3.1   Status Display Mode (Default Display) 
The Status Display Mode displays seven “screens” of information. Motor 
Currents (3 phases), Remaining Thermal Capacity, Ground Current, 
Remaining Time on the Process Timer, and Time Base of the Time 
Clock Controller. This is also the entry screen for going into the Program 
Mode. 
Status mode: 
[0000.] The initial display on power up is four digits and the decimal. 
This indicates the motor current for Phase A of the motor. 
[0000] Scroll UP to display four digits only (no decimal). This indicates 
the motor current for Phase B. While viewing Phase B, press the UP 
arrow again to view Phase C current. 
[G000] Scroll UP to display the “G”. This indicates that this value is the 
current flowing to ground on the motor leads. 
[H000] Scroll UP to display the “H”. This indicates that this value is the 
remaining thermal capacity percentage of the motor (i.e. H070 = 70% 
remaining thermal capacity) 
[0000] Scroll UP again to display the Process Batch Timer (described in 
Section 5.6.7). If this entire screen is flashing, the Timer is active. 
[00.00] Scroll UP to display two pairs of digits separated by a point: This 
indicates the time base of the Time Clock Controller (described in 
section 5.6.7). If the display shows [00.00], the TCC is not enabled. This 
follows the time settings in F075 – F080. 
Example: Figure 5.3.1 
Reading the Status Display 
[0120.]  Indicates Phase A is drawing 120 amps.  
Press the UP arrow 
[0121]  Indicates Phase B is drawing 121 amps. 
NOTE: Decimal points are not present in the 
readouts for Phases B and C
Press the UP arrow 
[0120]  Indicates Phase C is drawing 120 amps. 
Press the UP arrow 
[G002]  Indicates that there are 2 amps of current flowing 
to ground in the motor leads or motor. 
Press the UP arrow 
[H083]  Indicates the motor has 83% of its thermal capacity 
remaining (H = Heat). 
Press the UP arrow 
[0060]  Indicates there is 60 minutes remaining on the 
Process Timer. If flashing, the timer is active. 
Press the UP arrow 
[13.30]  Indicates the time base of the Time Clock 
Controller is 1:30 PM (24hr time). If flashing, the 
time clock is active and pending the next event.
 
Press the UP arrow 
[0120.]  Loop back to Phase A current indication