F069= Reserved 
 
5.6.12    
System Settings 
The following functions set operator interface controls and unit 
programming. Also contained here are the Clock settings used for 
history functions. Change the Clock settings if accurate time values are 
important. 
F070 =  Parameter Lock / User Password 
Factory Setting = 0 (disabled) 
Range = 0 – 999
 
Use only when necessary to prevent unauthorized access. 
Provides users with the ability to prevent unauthorized 
operators from making changes to the programmed functions. If 
you do NOT need to take advantage of this feature, do not enter 
anything into this function. The factory default is disabled, and 
no Password is necessary to make changes to the program. 
See Appendix 3 at the end of this manual for detailed instructions 
on using and altering the Parameter Lock / User Password 
feature. 
 
F071 =  Emergency Clear / Reset 
Factory Setting = 0 (disabled) 
Range = 0 – 2
 
This Function serves two purposes. It can clear the memory 
values used for lockouts and overload protection, and it can 
reset all functions to the factory default settings. This is a “One-
Shot” feature, so when another value is entered as shown 
below, this function automatically returns to the default state. 
ƒ  When F071 = 0, the feature is disabled.  
ƒ  When F071 = 1, the values stored in the Thermal Register and all of 
the Lockout Timers will be cleared. This will allow an emergency 
restart
 without having to wait for proper cool down time or lockout 
timers to expire. 
    WARNING
  
Clearing the Thermal Register to allow restarting without proper cool-down time after an 
Overload Trip will risk motor damage and fire. Use only where emergency restart is 
necessary with knowledge of these potential hazards.
 
 
ƒ  When F071 = 2, the values of all functions will be reset to the 
factory default settings. Use this feature when settings conflict or 
have been tampered with. This is also useful when you lose track of 
experimental settings and wish to start over. It will also be used to 
clear the Fault History. 
ƒ  NOTE:  
This will not reset F070 = Parameter Lock / User Password. See 
Appendix 3 for resetting this feature. 
 
F072 = Reserved