          Digital Solid State Soft Starters   18 – 1250A 
56 
5.6.10    
Output Relays 
There are three programmable relays (rated 240VAC, 5A, 1200 VA) in 
the TE Series. They can be programmed for change of state indication 
for any one of the 25 conditions identified in the following chart. 
F060 =  Aux Relay 1: Form C (SPDT) 
Factory Setting = 1 (Run / Stop) 
Range = 1 - 26 (See list)
 
Use to program the desired operation for Relay # 1. 
F061 =  Aux Relay 2: Form C (SPDT) 
Factory Setting = 2 (At Speed / Stop) 
Range = 1 - 26 (See list)
 
Use to program the desired operation for Relay # 2. 
F062 =  Aux Relay 3: Form A (SPST, N.O.) 
Factory Setting = 16 (Any Trip, 5 - 15) 
Range = 1 - 26 (See list)
 
Use to program the desired operation for Relay # 3. 
F063 =  Aux Relay Delay Timer for Settings 23 – 26  
Factory Setting = 0 (Disabled) 
Range = 1 – 999 seconds, or 0 (Disabled) 
Use to program the desired On Delay for any Aux. Relay that 
has been programmed for Settings 23 through 26 from the chart 
below. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
F064 = Reserved 
Setting 
Relay Operation Description 
Run / Stop (Changes on Start Command, resets on Stop) 
At Speed / Stop 
At Speed / End of Decel 
Start / End of Decel 
5 Short 
SCR 
Trip 
Phase Loss Trip 
7 Shunt 
Trip 
OL (Motor Thermal Overload) Trip 
OT (Starter Thermal Over Temperature) Trip 
10 
Short Circuit Trip 
11 
Current Unbalance Trip 
12 
Over Current (Shear-Pin) Trip 
13 
Under Current Trip 
14 Ground 
Fault 
Trip 
15 Phase 
Rotation 
Trip 
16 
Any Trip (#5 - #15) 
17 
Any Trip, (#5-#15) 
flashing output* 
18 
Coast Down Time Lockout 
19 
Starts Per Hour Lockout 
20 
Time Between Starts Lockout 
21 
Any Lockout (#18-#20) 
22 
Run Timer (F030) Engaged 
23 
Run / Stop with On-delay from F063 
24 
At Speed / Stop with On-delay from F063 
25 
At Speed / End of Decel with On-delay from F063 
26 
Start / End of Decel with On-delay from F063 
*NOTE: Flash rate for Setting #17 is ½ second On and Off
Table 5.6.10:  Output Relay Programming