Appendix 5 (cont.) External OL Relay Applications 
SPECIAL MOTOR APPLICATIONS 
 2S2W Motors 
2 speed / 2 winding motor applications require a separate OLR sized for 
each set of windings. These would need to be external OLRs. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
In this example:  
The TE Series is used ahead of an existing 2S2W starter, which 
already has separate OLRs for each speed. Dry Aux. contacts of the 
2S2W starter are used to provide a Run command to the TE Series so 
that all existing controls can be used. In addition, another dry Aux. of the 
Fast contactor is used to select Ramp 2. When started in Slow, Ramp 1 
(default) is used. If started in Fast, different ramp settings are necessary 
so Ramp 2 is used. (See section 4.2.5.a for Dual Ramp info.)  
Either OLR will trip the TE Series, which will display [ Ptc] and light 
the “Overload” LED.
TE Starter
.
Bypass
Contactor
"BP"
Disconnect
or
Circuit
Breaker
Solid State
.
Over Load
.
G
R /
L1
T /
L3
S /
L2
U /
T1
W /
T3
V /
T2
                                     Slow
Over Load
1
2
3
A1
A2
120VAC
 
 CONTROL POWER
 TE...-BP Series
Control Wiring
   TE-TB1
(24VDC)
VMX-TB-2
                                     Fast
 
Over Load
 
9
10
   TE-TB1
(PTC Input)
Slow
OL
Fast
OL
2S2W
MTR
MS
MF
 
MS
MF
2S2W Starter
 
(Logic not shown for clarity)
 
MS
MF
External 2-Speed 2-Winding (2S2W ) Starter
6
7
MF
 
   TE-
 
TB1
(
 
Ramp 2
 
)