Appendix 6 - Soft Starter Settings Record 
The following chart may be used to record the changes made to the factory settings. 
 
 
Fn #  Group 
Function Description 
Adjustment / Display Range 
Setting 
Increments
Factory 
Setting 
Setting Setting
F001 
M
o
to
r an
d
 O
v
e
rlo
a
d
 In
fo
Motor Nameplate FLA 
 
FLA must be programmed for 
starter to function. 
50-100% of Max Amp Rating. 
Upper limit of range automatically 
adjusts downward as Service factor 
is increased. 
1 amp 
 
 
F002 
Motor Nameplate  
Service Factor 
1.00 - 1.30 SF 
0.05 
1.0 SF 
 
 
F003 
Overload Class During Start 
NEMA / UL Class 5 - 20 
Class 10 
 
 
F004 
Overload Class During Run 
NEMA / UL Class 5 - 30 
Class 10 
 
 
F005 Overload 
Reset 
0 = Manual 
1 = Auto 
2 = Disabled Overload 
(Manual) 
 
 
F006-9 
Reserved for factory use
 
 
 
 
 
 
F010 
Startin
g
 an
d St
oppi
ng M
ode
s
 
Ramp Type Selection 
 
VR = Voltage Ramp 
CR = Current PID Ramp 
1 = Ramp 1, 2 = Ramp 2 
Setting 1 = VR1 + VR2 
Setting 2 = CR1 + CR2 
Setting 3 = VR1 + CR2 
Setting 4 = CR1 + VR2 
1  
 
VR1+VR2 
 
 
F011 
Initial Torque (VR) of Ramp 1 
0-100% Line Voltage 
1% 
60% 
 
 
F012 
Initial Torque (CR) of Ramp 1 
0-600% Motor
 
Current
 
1% 200% 
 
 
F013 
Accel Ramp Time of Ramp 1 
1-120 seconds 
1 second 
10 
seconds 
 
 
F014 
Max Current Limit of Ramp 1 
200 - 600% Motor
 
Current
 
1% 350% 
 
 
F015 
Initial Torque (VR) of Ramp 2 
0-100% Line Voltage 
1% 
60% 
 
 
F016 
Initial Torque (CR) of Ramp 2 
0-600% Motor
 
Current
 
1% 200% 
 
 
F017 
Accel Ramp Time of Ramp 2 
1-120 seconds 
1 second 
10 
seconds 
 
 
F018 
Max Current Limit of Ramp 2 
200 - 600% Motor
 
Current
 
1% 350% 
 
 
F019 
Jog M
odes
 
Voltage Jog 
5 – 100% Line Voltage 
1% 
50% 
 
 
F020 
Time of Voltage Jog 
1 – 20 Seconds 
1 second 
10 
seconds 
 
 
F021 
Current Jog 
100 – 500% Motor
 
Current 1% 
150% 
 
 
F022 
Kick 
Mode
 
Kick Start Voltage 
0 = Disabled, or  
10 - 100% Line Voltage 
1% 
Disabled 
 
 
F023 
Kick Start Time 
0.1 - 2 Seconds 
0.1second 
0.8 sec