Output on bypass  
UPS has switched to automatic or manual bypass mode  
or [end of bypass alarm] 
 
ω 
Communication failure 
Communication between Network Management Card/Proxy and 
UPS (or NSM) has failed 
or [Communication between Network Management Card/Proxy 
and UPS is restored] 
7.8.2.2  Protection alarms  
These alarms are mainly dedicated to trigger operating system shutdown actions: 
 
ω 
Shutdown criteria is reached 
One of the criteria for which the system should be shutdown has 
been reached 
 
ω 
Redundancy lost  
The installation has no redundancy source available anymore 
or [The installation has one or several redundancy source 
available]
 
 
ω 
Protection lost 
The number of sources ensuring your installation protection is not 
sufficient 
or [The number of sources ensuring your installation protection is 
sufficient] 
 
7.8.2.3  Multi UPS Systems and Notification Alarms  
With default configuration, the Network Shutdown Module considers that the “Notification Alarms” don’t trigger 
the shutdown. (only the notification action is performed). 
  
Anyway it is possible to configure a “Shutdown action” when a “Notification Alarm” event is received.  
In this case: 
ω 
The first alarm reception (from one of the UPSs) will trigger the system shutdown.
 
 
7.8.2.4  Multi UPS Systems and Protection Alarms  
ω 
Shutdown criteria is reached. 
With default configuration, the Network Shutdown Module triggers the shutdown when this event is 
received. 
 
Anyway it is possible to configure a “Shutdown” action when the following events are received.  
 
ω 
Redundancy lost alarm  
If the user configures a “Shutdown action” when a “Redundancy lost” event is received, the shutdown will 
occur when the installation has no redundant source available anymore.  
The redundancy Level is configured in Configuration-> Power Devices screen   
Following Alarms are taken into account for this alarm :  
>
 UPS fault (internal fault or battery fault) 
>
 Communication failure, 
>
 Output on bypass,  
>
 UPS Stopped. 
 
ω 
Protection Lost Alarm 
If the user configures a “Shutdown action” when a “Protection Lost” event is received, the shutdown will 
occur when the number of sources ensuring your installation protection is not sufficient.  
>
 Only following UPS faults are taken into account (internal fault or battery fault). 
>
 The By-Pass events (Automatic or Manual) for maintenance reasons are not taken into account.