HP Performance Optimized Data Center (POD) 40cp Benutzerhandbuch

Seite von 63
 
Specifications 53 
Environmental specifications 
 
Features Specifications 
Operating temperature 
-18ºC to 54ºC (0ºF to 130ºF) 
Non-operating 
temperature* 
2ºC to 54ºC (35ºF to 130ºF) 
Transit temperature** 
-30ºC to 60ºC (-22ºF to 140ºF), up to 72 hours 
Operating humidity 
 
15% to 80% relative noncondensing 
 
26ºC (79ºF) maximum wet bulb temperature 
Non-operating humidity* 
 
5 to 95% relative noncondensing 
 
39ºC (102ºF) maximum wet bulb temperature 
Operating altitude 
-76.2 to 3,048 m (-250 to 10,000 ft) 
Non-operating altitude 
-76.2 to 9,144 m (-250 to 30,000 ft) 
 
*For non-operating specifications, consider the temperature of computer and IT equipment inside the HP POD. 
**The HP POD must be drained before it is moved to a new location. 
For areas prone to freezing, consult HP for applicable operating solutions and evaluate water lines as described in 
) section of this document. 
 
Water distribution kit specifications 
  
Feature Specification 
Dimensions 
10 ft x 8 ft x 9 ft 
Tank capacity 
7.8 gal 
Pumps electrical 
480V, 3-phase, 60 Hz 
Pumps flow 
240 gal/min 
Chemical pot feeder 
capacity 
10 gal 
 
For more information, see Water specifications (on page