HP Performance Optimized Data Center (POD) 40cp Manuel D’Utilisation
Specifications 53
Environmental specifications
Features Specifications
Operating temperature
-18ºC to 54ºC (0ºF to 130ºF)
Non-operating
temperature*
temperature*
2ºC to 54ºC (35ºF to 130ºF)
Transit temperature**
-30ºC to 60ºC (-22ºF to 140ºF), up to 72 hours
Operating humidity
•
15% to 80% relative noncondensing
•
26ºC (79ºF) maximum wet bulb temperature
Non-operating humidity*
•
5 to 95% relative noncondensing
•
39ºC (102ºF) maximum wet bulb temperature
Operating altitude
-76.2 to 3,048 m (-250 to 10,000 ft)
Non-operating altitude
-76.2 to 9,144 m (-250 to 30,000 ft)
*For non-operating specifications, consider the temperature of computer and IT equipment inside the HP POD.
**The HP POD must be drained before it is moved to a new location.
**The HP POD must be drained before it is moved to a new location.
For areas prone to freezing, consult HP for applicable operating solutions and evaluate water lines as described in
) section of this document.
Water distribution kit specifications
Feature Specification
Dimensions
10 ft x 8 ft x 9 ft
Tank capacity
7.8 gal
Pumps electrical
480V, 3-phase, 60 Hz
Pumps flow
240 gal/min
Chemical pot feeder
capacity
10 gal
For more information, see Water specifications (on page