Troubleshooting and Pen Alignment 
 
 
of Recorder with Display 
12/03 
DR4300 Circular Chart Recorder Product Manual 
185 
8.5.7  Troubleshooting Relay Output  
Procedure 
Table 8-11 explains what to do if the displayed output does not agree with the single relay or dual relay 
control output.   
 
Table 8-11  Troubleshooting Relay Output Failure Symptoms 
Step 
What to do 
How to do it or  
where to find the instructions 
Be sure the recorder is configured for 
relay output. 
Refer to Section 4 – Configuration, Startup, and 
Operation of Recorder with Display.
 
Be sure all the recorder and control 
related data is correct. 
Refer to Section 4 – Configuration, Startup, and 
Operation of Recorder with Display.
  
Check that the applicable output relay 
actuates properly. If it does, go to step 4. 
Put the recorder into manual mode and adjust 
the output manually to raise or lower the PV 
around the setpoint. Listen for the click of the 
relay as the PV moves in either direction. 
Observe OUT 1 or OUT 2 value on the front 
display. 
4  
Check the field wiring. 
Refer to Section 2 – Installation.  
Replace the relay. 
Refer to Section 9 – Replacing Hardware 
Assemblies.
 
Replace the printed circuit assembly for 
the pen channel having the problem. 
Refer to the replacement procedure in Section 9 
– Replacing Hardware Assemblies.