Cabling and connections 
29(96) 
 
 
 
6.1.1  Cabling 
Use cables with heat resistance of at least +70
°
C. The cables and the fuses must be dimensioned 
according to the tables below. Installation of cables according to UL regulations is presented in Chapter 
6.1.4. 
The fuses function also as cable overload protection. 
These instructions apply only to cases with one motor and one cable connection from the frequency 
converter to the motor. In any other case, ask the factory for more information. 
 
 
1
st
 environment 
(restricted 
distribution) 
2
nd
 environment 
 
 
 
Cable type 
Level H/C 
Level L 
Level T 
Level N 
Mains cable 
Motor cable 
3* 
Control cable 
Table 6-1. Cable types required to meet standards. 
Level C 
=   EN 61800-3 (2004), category C1 
 
 
EN 61000-6-3 
 
Level H 
=  EN 61800-3 (2004), category C2 
 
 
EN 61000-6-4 
Level L 
=  EN61800-3 (2004), 2
nd
 environment (industrial) 
Level T: 
 
See page 9. 
Level N: 
See page 9. 
 
 
=  Power cable intended for fixed installation and the 
specific mains voltage. Shielded cable not required. 
 
 
(NKCABLES/MCMK or similar recommended) 
=  Power cable equipped with concentric protection wire 
and intended for the specific mains voltage. 
 
 
(NKCABLES /MCMK or similar recommended). 
=  Power cable equipped with compact low-impedance 
shield and intended for the specific mains voltage. 
 
 
(NKCABLES /MCCMK, SAB/ÖZCUY-J or similar recommended). 
*360º earthing of both motor and FC connection required to meet the standard 
=  Screened cable equipped with compact low-impedance 
shield (NKCABLES /jamak, SAB/ÖZCuY-O or similar). 
 
 
In NXL HVAC (MF4 – MF6): A cable entry flange should be used when installing the motor cable at both 
ends in order to reach the EMC levels.  
 
Note: 
The EMC requirements are fulfilled at factory defaults of switching frequencies (all frames).