Honeywell NXL Benutzerhandbuch

Seite von 96
30(96) 
Cabling and connections 
Honeywell
Honeywell
Honeywell
Honeywell
 
 
 
6.1.1.1 
Cable and fuse sizes 
 
 
Terminal cable size (min/max) 
Frame 
Type 
I
[A] 
Fuse 
[A] 
Mains 
cable 
Cu [mm
2
Main terminal 
[mm
2
Earth 
terminal 
[mm
2
Control 
terminal 
[mm
2
Relay 
terminal 
[mm
2
MF2 
NXL0002 
10 
2*1.5+1.5 
0.5—2.5 
0.5—2.5 
0.5—1.5 
0.5—2.5 
MF3 
NXL0003—0006 
3-6 
16 
2*2.5+2.5 
0.5—2.5 
0.5—2.5 
0.5—1.5 
0.5—2.5 
Table 6-2. Cable and fuse sizes for NXL Compact, 208 - 240V 
Terminal cable size (min/max) 
Frame 
Type 
I
[A] 
Fuse 
[A] 
Mains 
cable 
Cu [mm
2
Main terminal 
[mm
2
Earth 
terminal 
[mm
2
Control 
terminal 
[mm
2
Relay 
terminal 
[mm
2
MF2 
NXL0001—0002 
1-2 
10 
3*1.5+1.5 
0.5—2.5 
0.5—2.5 
0.5—1.5 
0.5—2.5 
MF3 
NXL0003—0005 
1-5 
10 
3*1.5+1.5 
0.5—2.5 
0.5—2.5 
0.5—1.5 
0.5—2.5 
MF4 
HVAC03—09 
7—9 
10 
3*1.5+1.5 
1—4 
1—2.5 
0.5—1.5 
0.5—2.5 
MF4 
HVAC12 
12 
16 
3*2.5+2.5 
1—4 
1—2.5 
0.5—1.5 
0.5—2.5 
MF5 
HVAC16 
16 
20 
3*4+4 
1—10 
1—10 
0.5—1.5 
0.5—2.5 
MF5 
HVAC23 
22 
25 
3*6+6 
1—10 
1—10 
0.5—1.5 
0.5—2.5 
MF5 
HVAC31 
31 
35 
3*10+10 
1—10 
1—10 
0.5—1.5 
0.5—2.5 
MF6 
HVAC38—45 
38-
45 
50 
3*10+10 
2.5—50 Cu 
6—50 Al 
6—35 
0.5—1.5 
0.5—2.5 
MF6 
HVAC61 
61 
63 
3*16+16 
2.5—50 Cu 
6—50 Al 
6—35 
0.5—1.5 
0.5—2.5 
Table 6-3. Cable and fuse sizes for NXL, 380 – 500V 
 
Note! This cable recommendation is based on standard EN 60204-1 and PVC isolated cable where there 
is either one cable on a shelf in temperature of + 40°C or four cables on a shelf in temperature of + 30°C