Control Keypad 
63(96) 
 
 
7.4.3.2 
Keypad reference 
The keypad reference submenu (R3.2) displays and allows the operator to edit the frequency 
reference. The changes will take place immediately. This reference value will not, however, 
influence the rotation speed of the motor unless the keypad has been selected as the active 
control place. 
NOTE:
 The maximum difference between the output frequency and the keypad reference is 6 Hz. 
The application software monitors the keypad frequency automatically. 
 
 
See Figure 7-6 for how to edit the reference value (pressing the Enter button is not, however, 
necessary). 
 
7.4.3.3 
Keypad direction 
The keypad direction submenu displays and allows the operator to change the rotating direction of 
the motor. This setting will not, however, influence the rotation direction of the motor unless 
the keypad has been selected as the active control place. 
 
See Figure 7-7 for how to change the rotation direction. 
 
7.4.3.4 
Stop button activation 
By default, pushing the STOP button will always stop the motor regardless of the selected control 
place. You can disable this function by giving parameter 3.4 the value 0. If the value of this 
parameter is 0, the STOP button will stop the motor only when the keypad has been selected as 
the active control place. 
 
See Figure 7-7 for how to change the value of this parameter.