7.4.5  Fault codes 
The fault codes, their causes and correcting actions are presented in the table below. The shadowed 
faults are A faults only. The items written in white on black background present faults for which you 
can program different responses in the application. See parameter group Protections. 
Note! When you contact the factory or the distributor due to a fault, it is advisable to write down all 
fault texts and codes that appear on the keypad 
 
 
Fault 
code 
Fault 
Possible cause 
Correcting measures 
Overcurrent 
Frequency converter has detected too high a 
current (>4*I
n
) in the motor cable: 
− 
sudden heavy load increase 
− 
short circuit in motor cables 
− 
unsuitable motor 
Check loading. 
Check motor size. 
Check cables. 
Overvoltage 
The DC-link voltage has exceeded the limits 
defined in Table 4-3. 
− 
too short a deceleration time 
− 
high overvoltage spikes in supply 
Make the deceleration time longer. 
Earth fault 
Current measurement has detected that the 
sum of motor phase current is not zero. 
− 
insulation failure in cables or motor 
Check motor cables and motor. 
System fault 
-  component failure 
-  faulty operation 
Reset the fault
 
and restart. 
Should the fault re-occur, contact 
the distributor near to you. 
 
Undervoltage 
DC-link voltage is under the voltage limits 
defined in Table 4-3. 
− 
most probable cause: too low a supply 
voltage 
− 
frequency converter internal fault 
In case of temporary supply voltage 
break reset the fault and restart the 
frequency converter. Check the 
supply voltage. If it is adequate, an 
internal failure has occurred. 
Contact the distributor near to you. 
 
11 
Output phase 
supervision 
Current measurement has detected that there 
is no current in one motor phase. 
Check motor cable and motor. 
13 
Frequency 
converter under 
temperature 
Heatsink temperature is under –10°C 
 
14 
Frequency 
converter 
overtemperature 
Heatsink temperature is over 90°C.  
 
Overtemperature warning is issued when the 
heatsink temperature exceeds 85°C. 
Check the correct amount and flow 
of cooling air. 
Check the heatsink for dust. 
Check the ambient temperature 
(p2.6.8). 
Make sure that the switching 
frequency is not too high in relation 
to ambient temperature and motor 
load. 
15 
Motor stalled 
Motor stall protection has tripped. 
Check motor.  
Check that Pump or Fan is not 
jammed  
16 
Motor 
overtemperature 
Motor overheating has been detected by 
frequency converter motor temperature 
model. Motor is overloaded. 
Decrease the motor load. 
If no motor overload exists, check 
the temperature model parameters.