Control Keypad 
67(96) 
 
 
53 
Fieldbus fault 
The data connection between the fieldbus 
Master and the fieldbus board is broken 
Check installation. 
If installation is correct contact the 
nearest Honeywell distributor 
 
54 
Slot fault 
Defective option board or slot 
Check board and slot. 
Contact the nearest Honeywell 
distributor 
 
55 
Actual value 
supervision 
Actual value has exceeded or fallen below 
(depending on par. 2.7.22) the actual value 
supervision limit (par. 2.7.23) 
 
Table 7-4. Fault codes 
 
7.4.6  Fault history menu (H5) 
The Fault history menu can be entered from the Main menu by pushing the Menu button right when 
the location indication H5 is visible on the keypad display. 
 
All faults are stored in the Fault history menu in which you can browse through them using the 
Browser buttons. You can return to the previous menu anytime by pushing the Menu button left
 
The memory of the frequency converter can store a maximum of 5 faults in the order of appearance. 
The latest fault carries the indication H5.1, the second latest H5.2 etc. If there are 5 uncleared faults 
in the memory the next occurring fault will erase the oldest from the memory. 
 
Pressing the Enter button for about 2 to 3 seconds resets the whole fault history. 
 
Figure 7-9. Fault history menu 
 
STOP
I/O  term
READY
STOP
I/O  term
READY
STOP
I/O  term
READY
nxlk20.fh8
Push Enter to reset!