Enviro EA800 Benutzerhandbuch

Seite von 98
D-011-0152
73
Specifications
Base Unit and Sensor Specifications
The following table lists the specifications for the EA800 base unit, sensors, and accessories.
Table 14
Specifications
Item
Specification
Dimensions
Approximately 230 mm x 199 mm x 55 mm(“9.375 H x 8.125" W x 2.25" D)
Weight
Base Unit: 0.27 kg (0.6 lb.)
Wireless Sensors: 0.11 kg (0.26 lb.) with batteries
Mounting
The EA800 base unit is mountable directly to 3-gang standard electrical enclo-
sure using pre-drilled holes on the EA800 rear case.
The EA800 base unit and wireless sensors can be mounted to drywall or simi-
lar surfaces using the appropriate anchors (not included).
Case Material
ABS, UL94V-0 rated
EA800 Input (Operating) Volt-
age 1, 2, 3
+11 to +26VDC @ 
≤500mA current draw. Standard commercial filtered and 
regulated power supply suitable. Supplied by AC adapter (not included; see 
Accessories) or alarm panel.
Note: Power supply requirement does not include additional require-
ments for loads switched through alarm output relays where 
power is derived from EA800 EA400 terminal strip connections.
EA800 Aux Power Out
Equivalent to DC input voltage used: +11 to +26VDC 
(Maximum output current 0.5A).
EA800 Real-Time Clock Battery CR2032 (3V Cell)
Wireless Sensor Input Voltage
Either:
• +12VDC  @  <100mA current draw using a 2.1 mm barrel plug, center 
positive; OR 
• 2xAA Alkaline Batteries (1.5V Cell)
Wireless Sensor Radiating 
Power (minimum, at PCB 
antenna connector)
• EA800 base unit: -3.5 dBm
• Sensors: -2.5 dBm
Wireless Sensitivity:
(minimum at printed circuit 
board antenna connection)
• EA800: -94.5 dBm
• Sensors: -95.5 dBm
Low and High Limit Adjust Range:
(Winland thermistor sensors only)
Temperature: -80° C to 150° C
(-112° F to 302° F)
Note: The Low and High Limit Adjust Range is dependent upon the 
sensor being used. See “Accessories” on page 44.
Humidity: 5 to 95% RH
Note: The Low and High Limit Adjust Range is dependent upon the 
sensor being used. See “Accessories” on page 44.
Water Presence: No Alarm / Alarm
Sensors
Up to four wired sensors
Up to four wireless sensors
Cable Length to Wireless 
Multi-Function Sensor 
EA-WMFS
100 ft. maximum
Wired Temperature Sensor:
2-wire; maximum 304 m (1000 ft.) cabling length
Wired Humidity Sensor:
3-wire; maximum 304 m (1000 ft.) cabling length