For SB142 and SB242 Series, attach sensor/signal input cables as follows: 
a.  Strip outer jacket of cable back 1 ¼”-1 1/2” and remove all of the 
shielding. 
b.  Strip red, black, and (white) insulation back ¼”. 
c.  Remove each terminal plug from respective channel. 
 
Orientation is as follows: (see Figure 9) 
 
• Red (White in 4-20mA applications) insulated conductor wire is 
connected to socket (A). 
• Black insulated conductor wire is connected to socket (B). 
• White (Red in 4-20mA applications) insulated conductor wire is 
connected to socket (C). 
• Shield/Drain wire is connected to ground socket (GND). 
 
• Depress selected position button to open terminal for respective wire. 
(Small flat blade screwdriver is recommended). 
 
Note: (4) position (and optional 12 position) plug can only be inserted one 
way to ensure proper wiring. 
 
 
Installation considerations for Dual Output Switchbox: 
There are several options for consideration of installation of a Dual Output 
Switchbox. (Figure 9) 
 
Input signal options are: 
• Temperature and Dynamic Acceleration 
• Dual Vibration with 4-20mA Output and Dynamic output 
 
 