Fujitsu DX60S2 Benutzerhandbuch
![Fujitsu](https://files.manualsbrain.com/attachments/6c4642b33d2edbd09f94719c20a133aa0e862902/common/fit/150/50/80a45702a21fefb1823bce6851e87db450dccf7792cb572ebc8a90330a68/brand_logo.png)
Chapter 1 Hardware Configurations
1.5 Power Distribution Units (Only for Regions Other than EMEA&I)
1.5 Power Distribution Units (Only for Regions Other than EMEA&I)
ETERNUS DX60 S2 Disk storage system User’s Guide -Site Planning-
24
Copyright 2012 FUJITSU LIMITED
P3AM-5492-04ENZ0
■
Power distribution unit for DX60 S2 (AC200-240V, 2U, Max 6 enclosures connection)
There are 12 outlets.
Figure 1.27 Power distribution unit (AC200-240V, 2U, Max 6 enclosures connection)
The following table shows the specifications of a power distribution unit and the AC cables that
are provided.
are provided.
Table 1.9
Power distribution unit (AC200-240V, 2U, Max 6 enclosures connection) and
provided AC cable specifications
■
Power distribution unit for DX60 S2 (AC200-240V, 2U, Max 8 enclosures connection)
There are 16 outlets.
Figure 1.28 Power distribution unit (AC200-240V, 2U, Max 8 enclosures connection)
Item
Specifications
Power
Voltage
AC200 - 240V
Phase
Single
Frequency
50Hz/60Hz
Input cable
Connection type
Straight-through
↔ NEMA L6-20P
Length
4m
Quantity
2
Output cable
Connection type
IEC60320-C13
↔ IEC60320-C14
Length
3m
Quantity
12
Outlets (OUTPUT)
Outlets (OUTPUT)