Fujitsu DX60S2 Benutzerhandbuch

Seite von 62
Chapter 1  Hardware Configurations
  1.5  Power Distribution Units (Only for Regions Other than EMEA&I)
ETERNUS DX60 S2 Disk storage system User’s Guide -Site Planning-
25
Copyright 2012 FUJITSU LIMITED
P3AM-5492-04ENZ0
The following table shows the specifications of a power distribution unit and the AC cables that 
are provided.
Table 1.10 Power distribution unit (AC200-240V, 2U, Max 8 enclosures connection) and 
provided AC cable specifications 
Item
Specifications
Power
Voltage
AC200 - 240V
Phase
Single
Frequency
50Hz/60Hz
Input cable
Connection type
Straight-through 
↔ NEMA L6-30P
Length
4m
Quantity
2
Output cable
Connection type
IEC60320-C13 
↔ IEC60320-C14
Length
3m
Quantity
16