FieldServer FS-8704-14 Benutzerhandbuch

Seite von 30
FS-8704-14 EtherNet/IP Manual 
 
 
 
 
 
 
 
Page 10 of 30 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA   Web: www.fieldserver.com 
Tel: (408) 262 2299   Fax: (408) 262 2269   Toll Free: (888) 509 1970   email: support@fieldserver.com 
4.4.4  Driver Related Map Descriptor Parameter s – PCCC 
Column Title 
Function 
Legal Values 
EIP_Service 
Action to be performed 
Exec_PCCC  (Encapsulation  using 
Allen Bradley PCCC) 
EIP_Con_Typ  The type of data transfer required 
Explicit 
EIP_Path
*
 
Used to stipulate the path to the CPU in certain PLC’s.  Paths 
vary and are dependent on the structure of the network.  
Any  space  delimited  numerical 
value.   
Refer  to  vendor’s  device 
documentation. 
Also 
see 
0 0
 
File_Type 
Allen Bradley file type 
N Integer 
F Float 
O Output 
B Boolean 
I Input 
S Status 
File_Number  Allen Bradley file number 
Any valid numerical value 
Length 
Number  of  data  elements  to  be  mapped.    If  the  number  of 
data elements exceeds the Map Descriptor length, the list of 
data elements will be truncated and an error message will be 
printed  once  per  Map  Descriptor.    Refer  to  Appendix  C  for 
further information. 
For  any  given  Map  Descriptor 
there  can  be  200  Floats,  400 
Integers or 800 Bytes 
Address 
Address in the file 
Any 
valid 
numerical 
value 
between 0 to 255 
4.4.5  Timing Parameters 
Column Title 
Function 
Legal Values 
Scan_Interval  Rate at which data is polled  ≥0.001s