CONFIGURING THE FIELDSERVER AS AN ETHERNET/IP SERVER 
For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The 
information  that  follows  describes  how  to  expand  upon  the  factory  defaults  provided  in  the  configuration  files 
included with the FieldServer. 
This section documents and describes the parameters necessary for configuring the FieldServer to  communicate 
with an EtherNet/IP Client.  
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable 
the FieldServer for EtherNet/IP communications, the driver independent FieldServer buffers need to be declared in 
the “Data Arrays” section, the FieldServer virtual node(s) needs to be declared in the “Server Side Nodes” section, 
and  the  data  to  be  provided  to  the  Clients  needs  to  be  mapped  in  the  “Server  Side  Map  Descriptors”  section. 
Details on how to do this can be found below. 
Note that in the tables, * indicates an optional parameter, with the bold legal value being the default. 
5.1 
Server Side Connection Descriptors 
Section Title 
Connections 
Column Title 
Function 
Legal Values 
Adapter 
Adapter Name 
N1, N2
4
 
Protocol 
Specify protocol used 
EtherNet/IP 
 
Example 
//    Server Side Connections   
 
 
Adapters 
 
Adapter 
,Protocol 
N1 
,EtherNet/IP 
 
                                                                 
4
 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available 
on specific hardware.