FieldServer FS-8704-14 Benutzerhandbuch

Seite von 30
FS-8704-14 EtherNet/IP Manual 
 
 
 
 
 
 
 
Page 22 of 30 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA   Web: www.fieldserver.com 
Tel: (408) 262 2299   Fax: (408) 262 2269   Toll Free: (888) 509 1970   email: support@fieldserver.com 
Appendix A.6.1. 
FieldServer Configuration File  
//    Data Arrays 
 
 
// 
 
 
Data_Arrays 
 
 
Data_Array_Name   ,Data_Format   ,Data_Array_Length 
DA_Read          
,Float        
,50 
DA_Write         
,Float        
,50 
 
//    Client Side Connections   
// 
 
Connections 
 
Adapter  
,Protocol 
N1       
,Ethernet/IP 
 
//    Client Side Nodes   
 
 
// 
 
 
 
Nodes 
 
 
 
Node_Name  
,IP_Address     ,Protocol     
,Adapter 
EIP_01     
,192.168.1.9    ,Ethernet/IP   ,N1 
 
//    Client Side Map Descriptors 
 
 
 
 
 
 
 
// 
 
 
 
 
 
 
 
 
 
 
Map_Descriptors 
 
 
 
 
 
 
 
 
 
 
Map_Descriptor_Name   ,Scan_Interval   ,Data_Array_Name   ,Data_Array_Offset   ,EIP_CON_TYP  
,Node_Name   ,Function 
,EIP_SERVICE      
,EIP_PATH   ,EIP_TAG_NAME    ,Length 
PLC_TO_FIELDSERVER   
,0.1            
,DA_Read          
,0                  
,EXPLICIT     
,EIP_01     
,Rdbc     
,DATA_TABLE_READ  
,1 0       
,FS_Status      
,20 
FIELDSERVER_TO_PLC   
,0.1            
,DA_Write         
,0                  
,EXPLICIT     
,EIP_01     
,Wrbc     
,DATA_TABLE_WRITE 
,1 0       
,FS_Control     
,20 
 
These are the PLC Tag names that will be accessed in the PLC. 
The names must match the PLC tag name exactly. 
Appendix A.3 lists the paths for 
specific devices