FS-8704-14 EtherNet/IP Manual 
 
 
 
 
 
 
 
Page 23 of 30 
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA   Web: www.fieldserver.com 
Tel: (408) 262 2299   Fax: (408) 262 2269   Toll Free: (888) 509 1970   email: support@fieldserver.com 
Appendix A.6.2. 
The PLC Program   
The  PLC  program  example  below  shows  the  minimum  steps  necessary  to  program  communications  with  the 
FieldServer. Depending on the real intended application, additional steps may be necessary for completeness.  
When the FieldServer is polling the PLC, all that is needed is to configure the tags being accessed: 
 
  
Step 2 
 
 
Note that providing dedicated (long), flat structured (not UDT) tags for communicatons interface to the FieldServer 
is  preferable  to  polling  single  length  tags  in  the  PLC  as  it  allows  for  much  more  efficient  communications  and 
reduces  complexity  when  mapping  data  in  the  FieldServer.  It  is  better  to  think  of  these  tags  as  a  “I/O  Buffer” 
Interface that the real tags in the PLC get mapped to.  
Appendix A.7. Read/write structures and value of EIP_Structure_Handle : 
Some devices require that a specific value be used for the EIP_Structure _Handle field while writing the structure 
to them.  This value may be specified in the vendor documentation.  If any non-zero integer is used in a Read Map 
Descriptor  for  EIP_Structure_Handle,  the  value  will  be  updated  internally.    The  Map  Descriptor  can  then  be 
browsed to obtain this value.   Other devices do not validate this field when the structure is written by the third-
party device.  A summary of the procedures to obtain this value is presented below: 
FieldServer as a Client: 
 
Read:  
 
Use a value of 1, the driver will automatically update the field when a response is received from the 
device.  The Map Descriptor can then be browsed to obtain the value if required. 
 
Write: 
 
Use the value supplied by the vendor OR 
 
Use the value obtained in the Read Map Descriptor above OR 
 
Use any non-zero value if the other device doesn’t validate it. 
 
FieldServer as a Server: 
 
Read:  
 
Use the value supplied by the vendor OR 
 
Use the value obtained in the Read Map Descriptor above OR 
 
Use any value if the other device doesn’t validate it. 
 
Write: 
 
Not 
required 
– 
use 
any 
non-zero 
value 
if 
the 
parameter 
is 
specified. 
Avoid Using UDT 
Types.  The Data will 
be read but the exact 
placement of the data 
in the Tags and Arrays 
will be hard to 
determine 
Tag Length must be equal to or greater than the 
number of points being written/read