2.2.1. FieldServer 
Information – Settings Aspect 
Parameter 
Description 
Tier 
FieldServers have the ability to run as “multiple” FieldServers on 
one platform.  To differentiate between the different running 
applications, each of the applications is referred to as a Tier with a 
specific name. 
FieldServer_Name 
A name by which a FieldServer is identified - need not be unique. 
N1 IP Address 
The IP address of the N1 Ethernet Adapter. 
N1 Netmask 
Netmask of N1 Ethernet Adapter. 
N1 Gateway 1 
The IP address of the gateway that N1 Ethernet messages use if 
the destination IP is not found on the local network. 
N2 IP Address 
The IP address of the N2 Ethernet Adapter. 
N2 Netmask 
Netmask of N2 Ethernet Adapter. 
N2 Gateway 1 
The IP address of the gateway that N2 Ethernet messages use if 
the destination IP is not found on the local network. 
Cache_Age_Limit 
Maximum age of data in a cache Map Descriptor for immediate 
response to poll.  Default 5 minutes.  See Error! Reference source 
not found.
 
Cache_Time_To_Live 
The time that the FieldServer maintains the port expanded polling in 
Port Expander Mode.  Default 5 minutes.  See Configuration 
Manual for more information.  
Cache_Size 
The maximum number of cache Map Descriptors allowed. 
System_Node_ID 
Use is driver dependent.  Generally used to identify the FieldServer 
as a node when it is configured as a server. 
Network_number 
Displayed where a protocol requires the FieldServer to be assigned 
a network number (e.g. BACnet). 
Hot_Standby_Mode 
Where specified, this parameter defines the behavior of the standby 
FieldServer in Hot Standby mode.  In Mode 1 the FieldServer is 
completely passive; in Mode 2 the standby FieldServer polls the 
connected devices through alternate communication paths.  Refer 
to the Configuration Manual for more information. 
Port_Expander_Mode 
Indicates whether the port expander mode function is enabled or 
not. 
Cache_Map_Descriptor_ 
Scan_Interval 
Default is two seconds.   
If the value 65535 is displayed, then this is an error and it indicates 
that there is no setting. 
Hot_Standby_Designation 
Primary or Secondary.  On boot the primary tries to become the 
active and the secondary tries to become the standby FieldServer. 
This behavior may be different if the so called secondary 
FieldServer gets re-booted first. 
Hot_Standby_Pair_Name 
A name by which a pair of FieldServers configured as a Hot 
Standby pair is known.  When one of a pair boots, it broadcasts a 
message with its pair name in order to try and locate the other 
FieldServer that forms the hot standby pair.