shipped without the time or date set and hence the value shown here is
meaningless until the FieldServer time is synchronized with the computer’s.
2.3. 
O - Connection Overview  
This is one of the most important information screens provided by RuiNet.  It supplies 
information on communication between the FieldServer and remote devices.  A number of 
aspect screens are available, and some of the aspect screens have more than one page.  
Use the space bar to toggle between aspects and the PgUp, PgDn keys to toggle between 
pages of the same aspect.  The Connection Overview and Settings Aspect screens are 
depicted below.  The various parameters are described more fully in the tables that follow. 
 
 
 
 
 
 
Figure 2.4 – Connection Overview Screen 
Port / Adapter 
 
N1 = Network Adapter 
P1...P8 = Serial RS-232 Ports 
R1...R2 = Serial RS-485 Ports 
Push the R key to set all stats for all connections to zero.  This doesn’t affect the 
operation of the FieldServer, drivers or communications to remote devices. 
Displays the number of errors for 
each connection.  Occasional 
errors may indicate noise but 
may also indicate a systematic 
error. 
Every attempt is made to standardize the way in 
which drivers report stats but in some drivers 
unavoidable differences exist.  In general, however, 
Rx Msg and Tx Msg correspond closely when 
connection is healthy.
Connection number. - Type 
number to go to detail for that 
connection, e.g. type 01 to 
navigate to detail for connection 
port N1