InstallatIon
requIred aBIlIty
Installation  or  service  of  this  hot  water  generator  requires  ability 
equivalent to that of a licensed tradesman in the field involved pipe 
fitting in the steam or boiler water is required. See Qualified Installer 
or Service Agency on page 2.
teMperature-pressure relIef ValVe
This water heater is provided with a properly rated/sized and certified 
combination temperature - pressure relief valve by the manufacturer. 
The  valve  is  certified  by  a  nationally  recognized  testing  laboratory 
that maintains periodic inspection of production of listed equipment of 
materials as meeting the requirements for Relief Valves for Hot Water 
Supply Systems, ANSI Z21.22 • CSA 4.4, and the code requirements 
of ASME.
If replaced, the new valve must meet the requirements of local codes, 
but  not  less  than  a  combination  temperature  and  pressure  relief 
valve rated/sized and certified as indicated in the above paragraph. 
The new valve must be marked with a maximum set pressure not to 
exceed the marked hydrostatic working pressure of the water heater 
(150 psi = 1,035 kPa) and a discharge capacity not less than the 
water heater Btu/hr or KW input rate as shown on the water heater’s 
model rating plate.
For safe operation of the water heater, the temperature and pressure 
relief valve must not be removed from its designated opening nor 
plugged.  The  temperature-pressure  relief  valve  must  be  installed 
directly into the fitting of the water heater designed for the relief valve. 
Install discharge piping so that any discharge will exit only within 6 
inches (15.2 cm) above, or at any distance below the structural floor. 
Be certain that no contact is made with any live electrical part. The 
discharge  opening  must  not  be  blocked  or  reduced  in  size  under 
any  circumstances.  Excessive  length,  over  30  feet  (9.14  m),  or 
use of more than four elbows can cause restriction and reduce the 
discharge capacity of the valve.
No valve or other obstruction is to be placed between the relief valve 
and the tank. Do not connect discharge piping directly to the drain 
unless a 6” (15.2 cm) air gap is provided. To prevent bodily injury, 
hazard to life, or property damage, the relief valve must be allowed 
to  discharge  water  in  adequate  quantities  should  circumstances 
demand. If the discharge pipe is not connected to a drain or other 
suitable means, the water flow may cause property damage.
The Discharge Pipe:
• 
Shall not be smaller in size than the outlet pipe size of the valve, 
or have any reducing couplings or other restrictions.
• 
Shall not be plugged or blocked.
• 
Shall be of material listed for hot water distribution.
• 
Shall be installed so as to allow complete drainage of both the 
temperature-pressure relief valve and the discharge pipe.
• 
Must terminate a maximum of six inches above a floor drain or 
external to the building. In cold climates, it is recommended that 
the discharge pipe be terminated at an adequate drain inside 
the building.
• 
Shall not have any valve or other obstruction between the relief 
valve and the drain.
The  temperature-pressure  relief  valve  must  be  manually  operated 
at least once a year. Caution should be taken to ensure that (1) no 
one is in front of or around the outlet of the temperature-pressure 
relief  valve  discharge  line,  and  (2)  the  water  manually  discharged 
will  not  cause  any  bodily  injury  or  property  damage  because  the 
water may be extremely hot. If after manually operating the valve, it 
fails to completely reset and continues to release water, immediately 
close  the  cold  water  inlet  to  the  water  heater,  follow  the  draining 
instructions  in  this  manual,  and  replace  the  temperature-pressure 
relief valve with a properly rated/sized new one.
If you do not understand these instructions or have any questions 
regarding  the  temperature-pressure  relief  valve  call  the  toll  free 
number  listed  on  the  back  cover  of  this  manual  for  technical 
assistance.
closed water systeMs
Water supply systems may, because of code requirements or such 
conditions  as  high  line  pressure,  among  others,  have  installed 
devices such as pressure reducing valves, check valves, and back 
flow preventers. Devices such as these cause the water system to 
be a closed system.