GDA-1600 16-Channel Controller 
 
Instruction 5700-9001 
22 
3.3.1  Common Alarm Relay 1 & 2 
 
WARNING:  READ THIS SECTION CAREFULLY AND TEST ALL 
SETTINGS BY SIMULATING GDA-1600 INPUT CONDITIONS THAT 
SHOULD ACTIVATE THESE ALARM RELAYS! 
Common Relay 1 & Common Relay 2 menus are identical and therefore discussed 
only once.  It is very important to fully understand these menus since they determine the 
functions of each common relay.   
 
Figure 3.11 – Relay Menus 
 
Entries 
Description 
Group 
The  Group  menu entry offers additional flexibility by controlling which channels trip 
this menu’s common alarm relay.  The 3 choices are 1-16,  1-8  or  9-16.  Some 
applications have different types of sensors or sensors in different areas connected to 
the same GDA-1600 Controller.  In these cases, it may be undesirable for a sensor on 
channel 9 to trip the same relay as a sensor on channel 2.  The  Group  menus may 
restrict this.  For example, channels 1-8 might be set to trip common relay 1 while 
channels 9-16 trip common relay 2.  Another possibility is that channels 1-8 be set to 
trip common relay 1 while channels 9-16 trip relays on an optional discrete relay PCB 
configured for Alarm 1 (see section 4.2.2 on page 30). 
Failsafe 
Failsafe controls relay activation for this common relay.  Failsafe ON causes the relay 
to de-energize during alarm conditions and energize when there is no alarm.  Thereby, 
a power failure forces the relay contact to the alarm position.  Note the common Fault 
relay is always failsafe and may be monitored separately to indicate loss of power 
conditions in many applications. 
A1 Votes 
A1 and A2 Votes allows creation of logical AND function equations that control 
common relay 1 & common relay 2.  Default settings for common relay 1 are A1 Votes 
= 01 and  A2 Votes = 00,  which causes relay 1 to trip if any channel has an A1 level 
alarm active.  Default settings for common relay 2 are A1 Votes = 00 and A2 Votes = 01 
which causes relay 2 to trip if any channel has an A2 level alarm active.  Example:  If 
either default setting is modified such that A1 Votes = 02 and A2 Votes = 01, then any 
two channels must have an A1 level alarm active and any one channel must have an A2 
level alarm active to trip that relay.   
CAUTION:  One of the A1s and the A2 could be on the same channel.  These level alarms 
must come from a channel included in the Group entry described above. 
A2 Votes