Acknowledge  Turning  Acknowledge  ON (not available on Alarm 1) allows the common relay to be 
deactivated during alarm conditions by an Alarm Reset.  This is useful if an audible 
device is being driven by the relay. 
All relays are rated at 5 Amp for 28 VDC and 250 ~VAC RESISTIVE
 
 loads.   
 
IMPORTANT:  Appropriate diode (DC loads) or MOV (AC loads) 
snubber devices must be installed with inductive loads to prevent RFI 
noise spikes.  Relay wiring should be kept separate from low level signal 
wiring. 
3.3.2  Discrete Relay “Failsafe” Mode 
Discrete relay options (P/N 5700-0012) may also be configured to function in a Failsafe 
mode using the System Setup menu shown in Figure 3.12.  Entering YES causes these 
discrete relays to have energized coils when no alarm condition exists for the associated 
channel and de-energized coils when the alarm occurs.  Failsafe is useful for indicating 
failed relay coils and loss of power conditions. 
 
IMPORTANT:  Zoning jumpers  (P/N 5700-0012)  as seen in Figure 
4.4  should not be used when Discrete Relays menus are set for 
failsafe.  Zoning jumpers cause ANY relay in the zone to energize ALL 
other relays in the same zone.  Zoning of failsafe relays may be 
accomplished with wiring at the relay contact terminals. 
 
Figure 3.12 – Failsafe Mode 
3.3.3  Common Horn Relay & Local Piezo 
The GDA-1600 is equipped with a low decibel audible piezo which chirps when keys are 
pressed and may be configured to audibly indicate alarm conditions.  The common horn 
relay is similar to the common A1 & A2 common relays. 
 
Figure 3.13 – Common Horn / Local Piezo Options