Bacharach GDA-1600 Benutzeranleitung

Seite von 54
Instruction 5700-9001 
 
GDA-1600 16-Channel Controller 
31 
and do not require discrete relays for each of the 48 alarm events (16 A1s, 16 A2s & 16 
A3s).  If discrete relays are needed for all 48 alarms, then six PCBs are required. 
5 VDC power to the discrete relay option PCBs is normally supplied from the GDA-1600 
Controller via the slender I
2
C cables connected to J2 and J3.  However, I
2
C cables are 
limited in ability to carry this power further than a few feet without a significant voltage 
drop.  Some GDA-1600 applications with relays for all 48 alarms may require up to 6 
boards.  TB2 allows a heavier 5 VDC power cable to be connected from terminals on the 
back of the GDA-1600 front panel assembly, bypassing the I
2
C cable.  A 20AWG pair 
connected to only one of the several TB2s is sufficient when these boards are in close 
proximity to each other. 
All relays are rated at 5 Amp for 28 VDC and 250 ~VAC RESISTIVE loads.   
!
 
IMPORTANT:  Appropriate diode (DC loads) or MOV (AC loads) snubber 
devices must be installed with inductive loads to prevent RFI noise spikes.  
Relay wiring should be kept separate from low level signal wiring. 
4.2.3  Optional *Bridge Sensor Input Board #5700-0011 
 
An  optional 8-channel, 12 bit Bridge Sensor Input board allows these popular gas 
detectors to be connected directly to the GDA-1600  without additional signal 
conditioning or transmitters.  Fault supervision circuitry forces the GDA-1600  into a 
FAULT condition upon sensor failure or removal. 
This option may also be configured to accept 4-20mA inputs for mixing bridge sensors 
and current loops into the same board.  Placing any channel’s 2-position LEL/4-20mA 
jumper into 4-20mA position and installing the associated precision 100 ohm socketed 
resistor allows 4-20mA signals to be applied to its C & A terminals.   
Channels receiving input data from this board should have the Data From: menu set for 
Sensor,  as described in section 3.2.4.  This activates Cal Mode  menus,  described  in 
section 3.2.7, which are needed to zero and span sensor readings.  After performing the 
one time only Initial Setup  as described below, all subsequent calibrations are by the 
GDA-1600’s electronic Cal Mode menus. 
*Catalytic sensors connected directly to the GDA-1600 should be limited to ranges of 0-1000ppm.