GDA-1600 16-Channel Controller 
 
Instruction 5700-9001 
32 
 
Figure 4.4 – Discrete Relay PCB 
4.2.4  Catalytic Bead Sensor Initial Setup 
Catalytic bead sensors vary widely in power requirements and sensitivity.  It is therefore 
important to configure each channel to match the sensor with which it will operate. 
1. 
Apply power to the system prior to connecting sensors.  Note this PCB requires 
24VDC power be connected to its TB2 terminals 1 & 2 as shown in Figure 4.5.  
Suitable fused power is available from the Main I/O board’s TB2 terminal 10 & 
12 (see Figure 4.2).  Measure the voltage between each channel’s A and R 
terminals and set the Voltage Adjust  potentiometers for the correct sensor 
excitation voltage.  This may range from 1.5 volts to 7.5 volts depending upon 
sensor specifications.   
!
 
WARNING:  Sensors may be damaged by accidental over voltage 
conditions.  It is recommended the Voltage Adjust potentiometer screws 
be covered by a dollop of RTV or similar material after completion of 
this procedure to avoid accidental over voltage conditions. 
2. 
Remove system power and connect sensor wires to the R-C-A terminals.  Reapply 
system power and confirm correct voltage across each sensor’s A & R terminals.