Bacharach GDA-1600 Benutzeranleitung

Seite von 54
Instruction 5700-9001 
 
GDA-1600 16-Channel Controller 
37 
5  System Diagnostics 
System Diagnostic Mode shown in Figures 5.1 and 5.2 may be entered during normal 
operation from the Setup menu.  The entry menu indicates firmware revision and offers 
useful routines for testing front panel LED’s, relays, serial ports and analog I/O.  It is 
exited manually by pressing NEXT  and automatically if no keys are pressed for 5 
minutes. 
!
 
IMPORTANT:  CHANNEL INPUT DATA IS NOT PROCESSED DURING THE 
DIAGNOSTICS MODE.
 
It is possible to miss important input values while utilizing this mode and appropriate 
safeguards should be in place.  However, the Diagnostics Mode can prove invaluable 
when testing I/O since relays  and analog outputs may be stimulated without driving 
inputs to precise levels. 
 
Figure 5.1 – System Diagnostic Screens