Bacharach GDA-1600 Benutzeranleitung

Seite von 54
Instruction 5700-9001 
 
GDA-1600 16-Channel Controller 
39 
6  MODBUS Descriptions 
6.1  MODBUS RS-485 Ports 
The  GDA-1600  is equipped with Master  (COMM 1), and Slave  (COMM 2),  Modbus 
RTU ports.  Port configurations are described in sections 3.2 and 3.3 of this manual.  
Section 6.2 defines register locations of data available via the GDA-1600 slave port. 
6.2  MODBUS Slave Register Locations 
The following tables describe the GDA-1600’s Modbus slave database.  Any portion of 
this data may be read by a Modbus master device such as a PC, PLC or DCS.  Since the 
Modbus port is RS-485, many GDA-1600s may be multi-dropped onto the same cable. 
Memory Integer ASCII: 
Notes:  ASCII may be read 2 characters at a time or in strings using a multiple register read. 
Sixteen character channel tag name: 
Type 
Channel 
First 
Last 
Read FC  Write FC  Notes 
Channel Tag 
40401 
40408 
n/a 
2 characters per register 
Channel Tag 
40409 
40416 
n/a 
2 characters per register 
Channel Tag 
40417 
40424 
n/a 
2 characters per register 
Channel Tag 
40425 
40432 
n/a 
2 characters per register 
Channel Tag 
40433 
40440 
n/a 
2 characters per register 
Channel Tag 
40441 
40448 
n/a 
2 characters per register 
Channel Tag 
40449 
40456 
n/a 
2 characters per register 
Channel Tag 
40457 
40464 
n/a 
2 characters per register 
Channel Tag 
40465 
40472 
n/a 
2 characters per register 
Channel Tag 
10 
40473 
40480 
n/a 
2 characters per register 
Channel Tag 
11 
40481 
40488 
n/a 
2 characters per register 
Channel Tag 
12 
40489 
40496 
n/a 
2 characters per register 
Channel Tag 
13 
40497 
40504 
n/a 
2 characters per register 
Channel Tag 
14 
40505 
40512 
n/a 
2 characters per register 
Channel Tag 
15 
40513 
40520 
n/a 
2 characters per register 
Channel Tag 
16 
40521 
40528 
n/a 
2 characters per register 
 
Six character Eunits Tag: 
Type 
Channel 
First 
Last 
Read FC  Write FC  Notes 
EUNITS 
40529 
40531 
n/a 
2 characters per register; 3 registers per channel 
EUNITS 
40532 
40534 
n/a 
2 characters per register; 3 registers per channel 
EUNITS 
40535 
40537 
n/a 
2 characters per register; 3 registers per channel 
EUNITS 
40538 
40540 
n/a 
2 characters per register; 3 registers per channel 
EUNITS 
40541 
40543 
n/a 
2 characters per register; 3 registers per channel 
EUNITS 
40544 
40546 
n/a 
2 characters per register; 3 registers per channel 
EUNITS 
40547 
40549 
n/a 
2 characters per register; 3 registers per channel 
EUNITS 
40550 
40552 
n/a 
2 characters per register; 3 registers per channel 
EUNITS 
40553 
40555 
n/a 
2 characters per register; 3 registers per channel 
EUNITS 
10 
40556 
40558 
n/a 
2 characters per register; 3 registers per channel 
EUNITS 
11 
40559 
40561 
n/a 
2 characters per register; 3 registers per channel 
EUNITS 
12 
40562 
40564 
n/a 
2 characters per register; 3 registers per channel 
EUNITS 
13 
40565 
40567 
n/a 
2 characters per register; 3 registers per channel 
EUNITS 
14 
40568 
40570 
n/a 
2 characters per register; 3 registers per channel 
EUNITS 
15 
40571 
40573 
n/a 
2 characters per register; 3 registers per channel 
EUNITS 
16 
40574 
40576 
n/a 
2 characters per register; 3 registers per channel