7  Enclosure Installation 
7.1  Panel / Rack Mount Enclosure 
The GDA-1600 shown in Figure 7.1 is a half width 19” rack enclosure.  It is supplied 
with hardware that allows mounting in either a full width 19” rack style cabinet or it may 
be panel mounted in a rectangular cutout.  Only two 8 channel I/O option PCBs such as 
analog input or discrete relays may be mounted directly to the back of the enclosure.  
Additional 8 channel I/O option PCBs  must be located external from the assembly on 
another mounting plate.  A 3 foot length of I
2
C cable is also supplied for this purpose.  
Weight is approximately 7 pounds.  Properly ground the enclosure and follow national 
and local electrical codes. 
RACK / PANEL MOUNT
(19” RACK SPREADER PLATES &
PANEL MOUNT BEZAL NOT SHOWN)
10.60
9.10
FRONT VIEW
5.22
SIDE VIEW
9.60
Note: Panel cut-out = 5.25 X 9.20
 
Figure 7.1 – Mounted Enclosure  
7.2  Wall Mount Fiberglass Enclosure 
The  GDA-1600  shown in Figure 7.2  is a fiberglass NEMA 4X  wall mount enclosure. 
Seven, 8-channel I/O option PCBs, such as analog input or discrete relay, may be 
mounted inside this enclosure.  It is suitable for mounting outdoors but an above mounted 
weather deflector shield is recommended.  Weight is approximately 17 pounds.  Figure 
7.3 provides important warning information concerning correct grounding procedures for 
non-metallic enclosures. Conduit entries are not provided so installers may place entries 
as needed.  Bottom or lower side areas are recommended.  Care must be taken to avoid 
drilling into circuit boards mounted inside the enclosure.  Properly ground the enclosure 