Bacharach GDA-1600 Benutzeranleitung

Seite von 54
GDA-1600 16-Channel Controller 
 
Instruction 5700-9001 
48 
energized by low battery conditions.  The actual battery voltage of each GDX-350 
RF may be seen in the 
INPUT DATA FROM screen. 
 
Calibrations performed at the GDX-350 RF force a transmission of 75 counts 
(negative 15.62%) which may be indicated on the GDA-1600’s LCD readout by 
In  Cal
  by using the “Marker Menu” described in section 2.2.4b.  Alarms are 
inhibited while the “Marker Value” of -15.62% is activated. 
 
Figure 8.4 
8.3.2  Wireless Modbus Slave Mode 
Wireless MODBUS allows one or many GDA-1600s to function as wireless Modbus 
slaves by connecting their RS-485 Modbus slave
The entire GDA-1600  Modbus database, including registers and supported Function 
Codes, is documented in section 5.1. 
 ports to a radio modem.  These wireless 
networks require a Modbus  master  such as a DCS, HMI or another GDA-1600  also 
equipped with a radio modem.  One transceiver must be designated as Server and all 
others as Clients.  No special configuration is required by the master or slave since this is 
a standard Modbus network.  However, radios must have the same 
Hop Channel and 
System  ID  settings to communicate.  Radio modules may only be configured when 
connected to the GDA-1600’s master port.  If it is necessary to modify 
Hop Channel 
and
 System ID settings, the radio module may be temporarily connected to the GDA-
1600’s master port for configuration then moved back to the slave port for operation. 
8.4  Wireless Modbus Master Mode 
GDA-1600  applications as a “Wireless Modbus master” are similar to the “Wireless 
Receiver” mode described in section 8.3 (on page 47) and wiring to the radio modem is 
identical.  The radio setup menus  described in section 8.2  may also be used for 
configuring hop channel and system ID settings.  The difference is each channel’s 
INPUT DATA FROM menu must be configured with the correct MODBUS values to 
match the slave device instead of 
Wireless RF900.  Wired and wireless inputs may be 
mixed between the GDA-1600’s sixteen channels so it is also possible to accept wired 
signals from analog input option PCBs described in section 4.2. 
This is a popular application when the Modbus slave is another remote GDA-1600 or our 
GDA-400 controller available with built in radio modem compatible with the GDA-1600