8.3  Wireless Receiver Mode 
Wireless Receiver mode is exclusively for wireless communication to our GDX-350 
RF wireless sensor transmitters.  In Receiver  mode the radio connects to the GDA-
1600’s  master  port and receives input data from up to sixteen GDX-350 RF sensor 
transmitters.  Wired and wireless inputs may be mixed between the GDA-1600’s sixteen 
channels so it is possible to also accept wired signals from analog input option PCBs. 
Use the 
WIRELESS  RF900  setting shown at center of Figure 8.3  ONLY  FOR 
COMMUNICATION TO GDX-350 RF WIRELESS TRANSCEIVERS
.  See section   
for setting up wireless networks with other Modbus slave devices. 
GDX-350 RFs transmit 200 counts for 0% and 1000 counts for 100% full scale readings 
so 
Input Min/Max menu values should be 200 and 1000.  The Remote ID menu entry 
must match the 
Remote Id address setting in the GDX-350 RF providing data to this 
GDA-1600  channel.  
Input Req  is typically set to VALUE but also allows a BATT 
entry into this field.  Entering BATT causes the channel to display (and alarm) from 
battery voltage levels at this GDX-350 RF.  Voltage level of the 3.6 volt lithium battery 
in this GDX-350 RF is also displayed on this screen. 
 
Figure 8.3 
8.3.1  Radio Status Alarms - Wireless Receiver Mode 
When an GDA-1600  channel’s 
INPUT  DATA  FROM  menu is set for WIRELESS 
RF900, in addition to processing the GDX-350 RF’s 10-bit “counts” value, it also 
receives status bits indicating 
Communications  Error,  Low  Battery  and 
Calibration
 
Communications Error – Each channel’s 30-minute trend screens (Figure 8.4) 
are very useful for diagnosing wireless problems since it indicates amount of time 
since the most recent transmission was received.  The down arrow on top of the 
trend screen resets to far right each time a transmission is received by that 
channel.  When not in alarm, GDX-350 RFs transmit each 5-minutes so the arrow 
should never progress past the 5-minute interval.  The GDA-1600  activates the 
channel’s FAULT alarm and indicates 
ComErr
  if no transmission has been 
received in 18 consecutive minutes. 
 
Low Battery status indicates the GDX-350 RFs integral 3.6V lithium D cell has 
dropped to below 3.3V and should be replaced very soon.  
LoBatt
 is indicated on 
the  GDA-1600’s LCD readout and the Alarm 3 LED flashes.  Relays are not