Chapter 4 - I/O Interfacing 
 
 
This chapter will explain "HIGH" and "LOW" states and show 
some general examples of how to interface to the I/O lines.  Caution 
must be taken not to exceed 485SDD16 specifications listed in 
Chapter 1 when interfacing to external devices.  Failure to stay 
within these specifications could result in damage to the unit and will 
void warranty. 
 
Digital Inputs 
 
As stated earlier, digital input lines are CMOS/TTL compatible 
and can only handle voltages from 0Vdc to +5Vdc. 
 
Digital inputs are used to sense a HIGH or a LOW state.  This 
can be accomplished via switch closures, contact closures, or a 
solid state digital signal.  When an I/O line, defined as an input, 
senses a voltage level above +2.0Vdc it will be considered "HIGH" 
and it's input state will be read as a "1".  Conversely, when an input 
senses a voltage level below +1.0Vdc it will be considered "LOW" 
and it's input state will be read as a "0". 
 
Inputs can also be used to sense AC voltages by using 
mechanical or solid state relays.  Solid state relays are available 
from many manufacturers. 
 
Figures 4.1 - 4.4 show examples of some typical input interfaces. 
 
 
 
Figure 4.1 - Switch Input 
18 485SDD16-1005 
Manual 
B&B Electronics  --  707 Dayton Road  --  Ottawa, IL  61350 
PH (815) 433-5100  --  FAX (815) 433-5104
 
 
Figure 4.2 - Solid State Input 
 
 
 
Figure 4.3 - Isolated Mechanical Input