Brocade Communications Systems Brocade MLX Series and Brocade Netlron XMR 53-1002373-02 Benutzerhandbuch

Seite von 452
78
Brocade MLX Series and NetIron XMR Hardware Installation Guide
53-1002373-02
Installing a Brocade MLXe-4 router
2
Connecting DC power
You can provide DC power for the Brocade MLXe-4 router by installing a DC-to-DC power supply. The 
DC-to-DC supply converts 48V-DC input from a power source to 12V-DC for your router.
DANGER
The procedure in this section is for qualified service personnel.
NOTE
Because there are multiple power supply vendors, the LED layout on your DC power supply may differ 
from what is shown in 
. However, the LED functions are identical.
Follow these steps to connect a DC power source.
1. Use a #1 Phillips screwdriver to remove the two screws that hold the transparent cover over 
the power supply lugs, as shown in 
.
FIGURE 50
The Brocade MLXe-4 DC power supply
2. Use a #2 Phillips screwdriver to remove the power lugs. 
3. Crimp #8 AWG power supply wire into the power lugs and reconnect the lugs to the power 
supply unit. Refer to 
CAUTION
For the NEBS-compliant installation of Brocade MLXe-4, Brocade MLXe--8, and Brocade MLXe-16 
routers with AC and DC systems, use a ground wire of at least 6 American Wire Gauge (AWG). The 
ground wire should have an agency-approved crimped connector (provided with the device) 
attached to one end, with the other end attached to building ground. The connector must be 
crimped with the proper tool, allowing it to be connected to both ground screws on the enclosure. 
Before crimping the ground wire into the provided ground lug, ensure the bare copper wire has 
been cleaned and antioxidant is applied to the bare wire.
1
Screws holding transparent cover
2 Power lug screws
DC OUT ALM
DC IN
1
2