D9412GV2/D7412GV2 | Program Entry Guide | 2.0  GV2MAIN 
EN | 30 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
 
Bat Fail/Res Rpt 
AC Tag Along 
Default: 
Yes 
Default: 
Yes 
Selection:  Yes or No 
Selection: 
Yes or No 
 
Yes 
Send AC messages as tag along 
events. 
No 
Do not send AC messages as tag 
along events. 
Send AC Reports only if any other event occurs while 
AC is off-normal.  
 
If AC Tag Along is set to Yes and a 
subsequent event is generated, the AC 
Fail Event is sent first, before sending 
any subsequent events. 
 
 
AC Tag Along is required for NFPA 
and UL 864 Commercial Fire systems. 
Be sure to program AC Fail/Res Rpt as 
No if AC Tag Along is programmed 
Yes
 
AC/Battery Buzz 
Default: 
No 
Selection: 
Yes or No 
Yes 
Initiates panel-wide trouble tone at 
all keypads. 
No 
Does not initiate panel-wide trouble 
tone at keypads 
Initiates a panel-wide trouble tone at keypads when 
AC fails or battery is low or missing. This program 
item does not prevent the SERVC AC FAIL or 
SERVC BATT LOW displays. 
 
 
To comply with NFPA standards and  
UL 864 requirements for Commercial Fire 
systems, program this item as Yes
 
 
 
If annunciating panel-wide troubles at a 
keypad with CC# Scope set to Panel 
Wide
 is undesirable, set CC# Trouble 
Tone
 to No. Refer to Section 2.10 
Keypad (Command Center)
 on page 51 
for keypad configurations. 
 
Battery Failure and Restoral Reports are 
sent to the central station. They are routed 
to the telephone number programmed for 
Power/Phone Events.   
Yes
Missing or 
shorted 
BATTERY 
MISSING  
Modem 
Report
Discharged 
below 12.1 
VDC 
BATTERY 
LOW  
Missing, 
shorted low 
battery 
TROUBLE 
ZONE 9 
BFSK 
Report
No 
Battery Failure and Restoral Reports are not 
sent to the central station. 
 
To comply with NFPA standards and  
UL 864 requirements for Commercial Fire 
systems, program this item as Yes
 
2.6 Printer 
Parameters 
Up to three D9131A Parallel Printer Interface 
Modules can be connected to the D9412GV2’s (one 
printer for the D7412GV2’s) SDI bus. Each printer is 
identified by an address of 17, 18, or 19. Options are 
available for Routing Reports and area assignments. 
Printer Address 
Default: 
17 
Selection:  17, 18, or 19 (only 17 is available 
for the D7412GV2) 
Enter the printer address you are programming. 
P## Area Assign 
Default: 
Selection:  1 to 8 
Assign an area to the printer programmed in Printer 
Address