Bosch Appliances Video Game Controller D9412GV2 Benutzerhandbuch

Seite von 158
D9412GV2/D7412GV2 | Program Entry Guide | 2.0  GV2MAIN 
EN | 32 
 
 
Bosch Security Systems, Inc. | 10/08 | F01U003636-04 
 
P## Fire Events 
Default: 
Refer to the program record sheet 
Selection:  Yes or No 
Yes 
All events in this group print at 
assigned printer. 
No 
No events in this group print at 
assigned printer. 
Use this prompt to determine whether these events 
print at assigned printer. 
P## Burglar Event 
Default: 
Refer to the program record sheet 
Selection:  Yes or No 
P## Access Event 
Default: 
Refer to the program record sheet 
Selection:  Yes or No 
P## User Event 
Default: 
Refer to the program record sheet 
Selection:  Yes or No 
P## Test Event 
Default: 
Refer to the program record sheet 
Selection:  Yes or No 
P## Diag Event 
Default: 
Refer to the program record sheet 
Selection:  Yes or No 
 
P## Auto Functions Event 
Default: 
Refer to the program record sheet 
Selection:  Yes or No 
P## RPS Event 
Default: 
Refer to the program record sheet 
Selection:  Yes or No 
P## Relay Event 
Default: 
Refer to the program record sheet 
Selection:  Yes or No 
 
P## Point Event 
Default: 
Refer to the program record sheet 
Selection:  Yes or No 
P## Usr Chng Evt 
Default: 
Refer to the program record sheet 
Selection:  Yes or No 
2.7 RPS 
Parameters 
Use these program items to enable remote 
programming software (RPS) functions in the control 
panel using the on-board phone connection. Two 
other methods of remote programming are available 
(external modem and LAN or WAN connection) using 
RPS. Refer to Section 6.4 SDI RPS Parameters on 
page 128 for more information on these types of 
remote programming. 
2.7.1  Uploading and Downloading Reports 
If the control panel is programmed to send reports in 
modem format, when RPS contacts the control panel 
and the passcode is incorrect, the control panel 
sends an RPS Access Fail Report to the D6500 or 
D6600. RPS Access Fail also occurs when the call is 
not terminated with either a Good-bye or Reset-bye 
command. 
RPS ACCESS OK is sent according to phone routing 
when a Good-bye command is entered from RPS to 
terminate the call.  
When a Reset-bye is used to terminate the call, a 
Remote Reset Report is sent to the D6500 or D6600, 
and an RPS ACCESS OK is placed into the control 
panel’s event log. Reports in the event log that were 
not sent before the Reset-bye are never sent to the 
D6500 or D6600.  
When RPS programming changes parameters, a 
Parameters Changed Report is sent to the D6500 or 
D6600. If any programming changes are made, 
perform a Reset-bye. 
When RPS contacts the control panel, the RPS 
passcode and DataLock code are verified. If the 
control panel’s passcode matches and the DataLock 
code does not, the control panel still generates a 
RPS Access OK Event; however, the session ends 
immediately. 
To prevent the control panel from answering the 
telephone automatically, enter Blank in the Answer 
Armed
 and Answer Disarmed prompts in this 
section.